ePAQ-9405 

User’s Guide 

UG-1084 

32  

   Test Panel 

Copyright © 2017 QEI 

 

NOTE 

The display will indicate in decimal format and display the actual count, as 
sampled (15-bit values). 

When additional accumulator points are to be examined, press the 

ENTER

 key, the 

accumulator points previously entered will scroll upwards to the next line on the 
display and all values will be frozen.  Then repeat step 1. by entering 

RC

 and the 

desired accumulator point numbers. This procedure can be continued to examine 
every accumulator point in the subsystem, if desired. 

NOTE 

Over a Remote based test panel connection, this command will continue to 
update the screen after the 5 minute inactivity timeout has elapsed.  When 
you attempt to exit from this command (by pressing Enter), you will be 
prompted to re-enter a valid username and password combination.  

 

15.11 Relay Control 

CAUTION

 

THE FOLLOWING PROCEDURE WILL ENERGIZE RELAYS CONNECTED 
TO CONTROL POINTS.  MAKE CERTAIN THAT EITHER IT IS SAFE TO 
COMMAND THE POINT OR THAT THE FIELD DEVICE IS 
DISCONNECTED FROM THE RELAY. 

 

NOTE 

When connected to the test panel via a Remote connection, Relay Control 
commands are not available for security reasons. 

 

Two (2) relay commands can be entered by the Test Panel to operate control relays.  
Command CN will control a function 1 (ON) relay and CF will command a function 2 
(OFF) relay.  

15.11.1  On Relay Operation (CN) 

To operate the function 2 (ON) relay on a control point (odd numbered 

relays K1-K15 typically), type 

CN

 (space) and the point number of the 

relay. Point numbers start with 0 (zero). 

6.  Press the 

ENTER

 key. The relay will operate.* All function 2 (ON) 

relays may be controlled one at a time by repeating steps 1. and 2., 
and using different point numbers. 
 

Содержание ePAQ-9405

Страница 1: ...UG 1084 ePAQ 9405 User s Guide December 2018...

Страница 2: ...scribed to improve reliability function or design QEI does not assume liability arising out of the application or use of any product or circuit described herein neither does it convey any license unde...

Страница 3: ...er s Guide ePAQ 9405 User s Guide Revisions i Revisions Revision Description Date A Initial Release April 19 2016 B Client and Server updates April 29 2016 C Formatting Update June 6 2017 D Changed QE...

Страница 4: ......

Страница 5: ...1 Port 1 J3 USB Maintenance Panel 9 7 2 Port 2 J4 RS 232 9 7 3 Port 3 J5 Fiber Optic 10 7 4 Port 4 TB5 RS485 10 7 5 Port 5 J6 or J7 Ethernet 100BaseFX 100BaseT 11 7 6 Port 6 J1 or J2 or TB4 Irig B Ti...

Страница 6: ...onnection Ethernet Port 27 15 5 Security 27 15 6 Help for Test Panel Commands 28 15 7 DATE and TIME Commands 29 15 8 Reading Analog Values RA 29 15 9 Reading Status Values RS 30 15 10 Reading Accumula...

Страница 7: ...with 1 msec Sequence of Events SOE and time tagging in critical environments where highly secure operation is required Local diagnostics and configuration are accomplished via a Maintenance Port USB...

Страница 8: ...nal block TB5 Port 5 100BaseFX Interface Ethernet IEEE 802 3u compliant Protocols IP TCP UDP Bit Rate Up to 100 Mbps Connector ST multimode J6 Port 5 10 100BaseT Interface Ethernet IEEE 802 3 complian...

Страница 9: ...Options Important See ordering information and Keying Source section elsewhere in this guide Analog Point Interface Addressability 4 points Scaling options 0 1mA 0 20mA 0 5Vdc Power Input Voltage 12...

Страница 10: ...0 or 277Vac Input power connections are made at terminal block TB1 H L L H TB1 PIN Name Description 1 Chassis Connection 2 Chassis Connection 3 L DC Neg AC Neut 4 L DC Neg AC Neut 5 H DC Pos AC Line 6...

Страница 11: ...bank of four DIP switches is available through the front panel Dip switches are used for application specific options see the appropriate ConfigWiz 2 0 addendum for further information The exception i...

Страница 12: ...here are six LEDs arranged as three Trip Close pairs for the three control points LED Name Function CONTROL 1 3 Control Relay Output Indication LEDs For each LED pair Left LED indicates TRIP relay coi...

Страница 13: ...TIVITY IRIG B Activity LED This LED turns on whenever a valid IRIG B time sync message is received by the ePAQ via unmodulated Fiber J1 or RS485 TB4 input or via modulated input J2 6 4 L R Local Remot...

Страница 14: ...Ethernet ports High Speed Link Network Activity L A HS R T R T RS 232 J4 Tx Rx Tx Rx J5 J6 10 100 J7 ETHERNET PORT 5 COMM PORT 3 PORT 2 PORT 4 R T RS 485 LED Name T R Dual LED arrays indicate TX and...

Страница 15: ...1 via ConfigWiz 2 0 to download configurations and flashload program link files 2 via Hyperterminal or other such terminal emulator program to gain access to included test panel functions For a list o...

Страница 16: ...r using ST connectors A wide variety of communications bit rates can be supported R T Tx Rx J5 COMM PORT 3 J5 ST Jacks Signal Name TX Transmit data output RX Received data input 7 4 Port 4 TB5 RS485 T...

Страница 17: ...100BaseT This single port accepts either a multimode fiber transceiver with ST connectors J6 or a shielded RJ45 jack for CAT5 cable J7 It supports either 100BaseFX Ethernet over fiber or 100BaseT Eth...

Страница 18: ...RJ45 PIN Signal Name 1 TX 2 TX 3 RX 4 5 6 RX 7 8 7 6 Port 6 J1 or J2 or TB4 Irig B Time Sync This single port accepts input from an Irig B receiver for time syncing the internal ePAQ 9405 timeclock Ti...

Страница 19: ...of momentary relays one for trip and one for close or as a single latching relay trip close See the ordering information to choose controls as momentary or latching on a per point basis 8 1 Momentary...

Страница 20: ...TB2B 2 Control Point 2 Close N O TB2B 3 Control Point 3 Close N C TB2B 4 Control Point 3 Trip COM TB2B 5 Control Point 3 Trip N O TB2B 6 Control Point 3 Trip N C TB2B 7 Control Point 3 Close COM TB2B...

Страница 21: ...Trip COM TB2A 2 Control Point 1 Trip N O TB2A 4 Control Point 1 Close COM TB2A 5 Control Point 1 Close N O TB2A 7 Control Point 2 Trip COM TB2A 8 Control Point 2 Trip N O TB2B 1 Control Point 2 Close...

Страница 22: ...configuration 6 12 5 11 4 10 3 9 2 8 1 7 STATUS 1 2 3 4 ANALOG 9 1 Connection Name TB3A 1 Status Point 1 TB3A 2 Status Point 1 TB3A 3 Status Point 2 TB3A 4 Status Point 2 TB3A 5 Status Point 3 TB3A 6...

Страница 23: ...e options as follows Keying source comes from an internal ePAQ 24Vdc isolated power source Keying source comes from the ePAQ input power source For example if the ePAQ is running on 48Vdc then the sta...

Страница 24: ...le See the ordering information to choose the appropriate analog scaling configuration 6 12 5 11 4 10 3 9 2 8 1 7 STATUS 1 2 3 4 ANALOG 10 1 Analog Connections Connection Name TB3C 1 Analog Point 1 TB...

Страница 25: ...CD A special ePAQ 9405 Template is required to configure the ePAQ 9405 using the ConfigWiz 2 0 software See the ConfigWiz 2 0 Users Guide UM 2018 and the ePAQ 9405 Addendum for more specific configura...

Страница 26: ...al Outline L A HS R T R T 16 15 14 6 12 5 11 4 10 3 9 2 8 J3 J2 Rx Tx RS 232 J1 J4 Tx Rx Tx Rx J5 J6 10 100 BASET J7 ACTIVITY IRIG PORT 6 ETHERNET PORT 5 COMM PORT 3 PORT 2 PORT 4 MAINT PORT 1 IRIG R...

Страница 27: ...1 05 12Vdc keying w internal non isolated keying voltage source Note 2 06 24Vdc keying w internal non isolated keying voltage source Note 2 07 48Vdc keying w internal non isolated keying voltage sour...

Страница 28: ...tage source is provided by the customer An isolated or non isolated source can be used The TB3C right most end terminals may be used as tie points for the customer s keying voltage The proper keying v...

Страница 29: ...ine no connection with the Master Subsystem testing of status analog accumulator pulse count and control points The test panel can also serve as a troubleshooting aid for the Remote Subsystem hardware...

Страница 30: ...points displayed can consist of the 4 hardware analog points connections at ePAQ terminal block TB3C as well as other analog points within the overall subsystem 15 3 2 Status Monitoring In this mode...

Страница 31: ...PC s HyperTerminal or other communications program The USB driver makes the ePAQ USB connection appear to the PC as a COM port connection Before installing the driver check which COM ports are alread...

Страница 32: ...d begins flashing 3 Connect the USB cable from the ePAQ to the PC 4 Start the PC HyperTerminal program 5 When prompted for New Connection name use ePAQ 9405 or similar 6 When prompted for connection p...

Страница 33: ...the ConfigWiz 2 0 software See the ConfigWiz 2 0 Guide for further information 5 The Port number is always 57222 6 After entering this information press the enter key on the PC and verify that a promp...

Страница 34: ...e as backups Using the test panel SAVE and RESTORE commands each configuration file can be stored in non volatile memory and recalled when needed Using ConfigWiz 2 0 the user can assign a unique ID st...

Страница 35: ...Current Date is Thu 09 21 2000 3 To enter or view the current time type TIME enter The following will be displayed Current Time Is 15 52 20 Enter New Time 4 To enter New Time type the new time in the...

Страница 36: ...the ENTER key the analog points previously entered will scroll upwards to the next line on the display and all values will be frozen not updated Then repeat step 1 by entering RA space and the desired...

Страница 37: ...ditional status groups points are to be examined press the ENTER key the status group points previously entered will scroll upwards to the next line on the display and all values will be frozen Then r...

Страница 38: ...ou will be prompted to re enter a valid username and password combination 15 11Relay Control CAUTION THE FOLLOWING PROCEDURE WILL ENERGIZE RELAYS CONNECTED TO CONTROL POINTS MAKE CERTAIN THAT EITHER I...

Страница 39: ...system documentation for further information 15 12Communication Checks Several test panel commands are associated with ePAQ communications testing The test panel can be used to identify port configura...

Страница 40: ...timeout has elapsed When you attempt to exit from this command by pressing Enter you will be prompted to re enter a valid username and password combination Example Type PRX 2 enter The Test Panel will...

Страница 41: ...display the version of software residing in the ePAQ type VER enter Example VER enter Display QEI ePAQ 9405 Link 80 013XXX XXX 3 22 16 Chksum 6320d4ca 15 15 TP Command This command invokes a software...

Страница 42: ...ropriate There are several forms of this command as follows 15 16 1 SOE Just entering SOE will cause all saved SOE events to be displayed on the test panel most recent first The listing can be termina...

Страница 43: ...le 0 Len 34 Maxlen 34 1c 1 Owner System 10 Table 0 Len 12c Maxlen 12c 1d 3 Owner ConfigWiz 9 Table 9 Len 838 Maxlen 838 20 11 Total Table Len 4676 15 18 SEC Security Logger This command list certain e...

Страница 44: ...isplays Network Information such as MAC address IP and Gateway adressses ePAQ 9405_A ETH Mac Addr 0 bd 33 6 68 22 IP 192 168 0 95 NM 255 255 255 0 GW 192 168 0 1 Cfg 1 0 0 15 20 PROFILE Command Enable...

Страница 45: ...onfiguration file This ID string will appear at the test panel user prompt to let the user know which configuration file is active ePAQ 9405_A SAVE B 15 22 RESTORE A or B Command See section above Thi...

Отзывы: