UG-1083 ePAQ-9400
-
Copyright © 2016 QEI.
Test Panel
29
NOTE
If a status group is not responding to interrogation, the word
FAIL
will be
shown instead of the 16 points on that group.
Sixteen (16) status points are displayed for each group with the first point (point 0)
located at the far right and the last point (point 15) located to the left.
For the ePAQ, the first point (in Group 0) is local/remote indication (0= remote, 1 =
local) and the second point is Irig time-sync signal status (1 = OK, 0 = no valid Irig
time-sync connection present.) The next sixteen points are the ePAQ front panel
hardware status input points (point 1 to point 16.) 0 (zero) on the display represents
an open status point, a 1 (one) represents a closed status point.
ePAQ-9400_A> RS 0 1
00000000 00000000 XXXXXXXX XXXXXX00
When additional status groups/points are to be examined, press the
ENTER
key, the
status group points previously entered will scroll upwards to the next line on the
display and all values will be frozen. Then, repeat step 1. by entering
RS
and the
desired status group numbers. This procedure can be continued to examine every
status group in the RTU, if desired.
NOTE
Over a Remote test panel connection, this command will continue to update
the screen after the 5 minute inactivity timeout has elapsed. When you
attempt to exit from this command (by pressing Enter), you will be prompted
to re-enter a valid username and password combination.
14.10
Reading Accumulator Values (RC)
The Test Panel can monitor up to eight (8) accumulator values at a time.
Type in
RC
(space) and the accumulator point number or numbers, not necessarily
in any order. Each number must be followed by a space. Point numbers begin with
point number 0 (zero).
Example entry for accumulator points:
RC 7 10 14 15
Display:
00230 00010 01462 00483