UG-1083 ePAQ-9400
-
Copyright © 2016 QEI.
Test Panel
33
14.13
Displaying Dip Switch States (DIP)
A test panel command is available for examining the state of the 16 dipswitches on
the ePAQ. Type
DIP
<enter> from the test panel. Dip switches are displayed in the
order that they appear on the front panel.
Example:
DIP <enter>
Display:
ePAQ-9400_A> DIP
1000
14.14
Displaying the Software Version (VER)
To display the version of software residing in the ePAQ, type
VER
<enter>.
Example
VER <enter>
Display
QEI ePAQ-9400 Link:80-009XXX-XXX 8/22/08 Chksum: 6320d4ca
14.15
TP Command
This command invokes a software monitor, which is useful in diagnosing different
types of problems.
Example
Type TP 15 <enter>
Display
Software Monitor running at level 15
The ePAQ will print error and informational messages (if any) on the test panel, while
in operation.
14.16
SOE Command
This command allows saved SOE events to be viewed.
SOE <[point number]> <count>
SOE events are displayed most recent first, in the following format:
soe
52 events available (in Ram)
11/10/2005 13:32:29.904 [20] Status4 OFF
11/10/2005 13:32:29.904 [19] Status3 OFF
11/10/2005 13:32:29.904 [18] Status2 OFF
11/10/2005 13:32:29.495 [2] Panel0Pt2 OFF