EZ Plate™ Storage Water Heater
13
PV500-64 12/14
LED Display Alarm Messages
Alarm messages are displayed in the upper LED readout and alternate with the default display. An alarm LED ICON
is also illuminated.
ALARM
MESSAGE
CAUSE
RESULTS OF ALARM CONDITION
RECOMMENDED
ACTION
“P1”
TP1 probe failure
Inlet temperature sensor is not connected or is
reading incorrectly. Call for heat and burner
modulation output signal will revert to low fire.
Check wiring and sensor
Terminals 14 & 17
“P2”
TP2 probe failure
Temperature sensor is not connected or is reading
incorrectly.
Check wiring and sensor
Terminals 15 & 17
“P3”
TP3 probe failure
Temperature sensor is not connected or is reading
incorrectly or flue gas temperature protection is
disabled.
Check wiring and sensor
Terminals 16 & 17
“HA”
High temperature limit setpoint
exceeded
Audible alarm sounds, operation continues.
Press any button to reset
(while alarming)
“LA”
Low temperature alarm
Audible alarm sounds, operation continues.
AL1
Digital input 1 is activated.
Unit de-energized after timer delay. Audible alarm
sounds.
Press any button to reset
(while alarming)
AL2
Digital input 2 is activated.
This alarm indication is dedicated to
the Alarm On Any Failure feature of
this product.
Unit de-energized after timer delay. Audible alarm
sounds. Alarm contacts close for remote indication
of alarm. Internal alarm register will communicate
an alarm condition though the Modbus RTU
communication link.
Press any button to reset
(while alarming)
AL3
Digital input 3 is activated.
Unit de-energized after timer delay. Audible alarm
sounds.
Press any button to reset
(while alarming)
Mn1
Maintenance alarm for output 1
Buzzer sounds, operation continues
Check wiring and sensor
Mn2
Maintenance alarm for output 2
Buzzer sounds, operation continues
Check wiring and sensor
Mn3
Maintenance alarm for output 3
Buzzer sounds, operation continues
Check wiring and sensor
“rtc”
The real time clock has lost its
setting
Energy saving function disabled
Reprogram clock
CONTROL
MESSAGE
CAUSE
RESULTS OF CONTROL CONDITION
NOTES
On
A call-for-heat condition
The burner operating sequence should begin.
If the burner does not operate,
check safety devices or
Remote Proving Interlock
Flashing
The remote enable/disable has
been triggered
The small flame icon will flash indicating the
standby state
The
R1-R2
terminals have
been opened by the remote
master control. The heater will
remain in standby.
Integral circulation pump
The integral circulation pump will operate until the
water temperature has equalized
Pump may operate before,
during or after the call-for-heat