EZ Plate™ Storage Water Heater
12
PV500-64 12/14
To View the Setpoint
• Push and release the
SET
key to see the set point value.
• To return to normal display, press
SET + UP
or wait 15 seconds without pressing any key.
To Change the Setpoint
• Push the
SET
key. The upper display will show the “St1” parameter name, while the lower display will show its
value.
• Use the
UP
or
DOWN
key to cycle through the parameter names.
• Push the
SET
key to modify a parameter value. The value starts flashing in the lower display.
• To change it push the
UP
or
DOWN
keys. Push the
SET
key again to confirm the value and pass to the setting
of next set point.
• Repeat the operations described at points 3, 4, 5.
•
To Exit:
press
SET + UP
or wait 15 seconds without pressing any key.
NOTE:
Each point has a time out of 15 seconds. If any key is pushed within 15 seconds the controller exits the set
points programming procedure.
NOTE
: The set value is stored even when the procedure is exited by waiting the time-out to expire.
To Change Other Parameters
• Push the
SET
and
DOWN
arrow simultaneously for 3 seconds.
• Select the required parameter. The name of the parameter is on the upper display; its value is on the lower
display.
• Press the
SET
key: the value of the parameter will start blinking.
• Use
UP
or
DOWN
to change the value.
• Press
SET
to store the new value and move to the following parameter.
•
To Exit
: Press
SET + UP
or wait 15s without pressing a key.