Page
89
Miscellaneous
When P210, 220, 230, 240, 250, 260, 270, 280, 290, 570 = 4 (Miscellan.)
When a relay is set to be
miscellaneous
relay, the
second parameter
determines its
function
.
P211, P221, P231, P241, P251, P261, P271, P281, P291, P571
Relay Function
,
This function allows the relay to work in relation to a clock and will be set to
activate in relation to Real Time or to provide a pulsed output in relation to a
predetermined count from the totaliser, the choices being as follows:
Options
Description
0 = Off (Default)
Relay
Off de-energised
1 = Clock
Relay will
energise ON
at a specified time
each day as set in Relay Setpoint 1 (P2
1
3,
2
2
3, 2
3
3, 2
4
3, 2
5
3, 2
6
3, 2
7
3, 2
8
3, 2
9
3,
5
7
3). And turns
OFF
,
de-energises
, after
the specified On Time period as set in Relay
Setpoint 2 (P2
1
4, 2
2
4, 2
3
4, 2
4
4, 2
5
4, 2
6
4,
2
7
4, 2
8
4, 2
9
4, 5
7
4)
2 = Totaliser
Relay will energise ON momentarily each
time the specified flow has passed as set in
Relay setpoint 1 (P2
1
3, 2
2
3, 2
3
3, 2
4
3, 2
5
3,
2
6
3, 2
7
3, 2
8
3, 2
9
3, 5
7
3), this parameter sets
the multiplication factor which will be
applied to the on board totaliser (P820) to
determine the switch point of the relay. E.g.
if the totaliser is set to totalise in cubic
metres and the relay is required to provide a
closure every 10,000 litres Relay setpoint 1
would be set to 10. Relay setpoint 2 (P2
1
4,
2
2
4, 2
3
4, 2
44
, 2
5
4, 2
6
4, 2
7
4, 2
8
4, 2
9
4, 5
7
4)
can be used to select the time the relay will
remain closed in seconds.
Содержание QUANTUM3
Страница 1: ...QUANTUM 3 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 14: ...Page 6 EU Declaration of Conformity ...
Страница 17: ...Page 9 The full dimensions of the enclosure are as shown below ...
Страница 21: ...Page 13 ...
Страница 22: ...Page 14 ...
Страница 48: ...Page 40 This page left blank intentionally ...