148
mA2 Trim
P896 mA2 Low Trim
If the remote device you are connected to is not calibrated, and not showing
the correct
low value
(reading), then you can trim it using this parameter. You
can either type in the offset directly, or use the arrow keys to move the output
up and down until you get the expected result (reading) on the remote device
that is connected.
P897 mA2 High Trim
If the remote device you are connected to is not calibrated, and not showing
the correct
high value
(reading), then you can trim it using this parameter.
You can either type in the offset directly, or use the arrow keys to move the
output up and down until you get the expected result (reading) on the remote
device that is connected.
mA2 Failsafe
P898 mA2 Fail-safe Mode
This parameter determines what happens to the mA output in the event of the
unit going into fail-safe mode. The
default
is to do the same as the
system
fail-safe
(
P808
), but this can be overridden to force the mA output to an
independent fail-safe mode as follows:
Option
Description
0 = Default
mA output will fail as per
P808
.
1 = Hold
mA output will retain its last known value.
2 = Low
mA output will fail to its
low
condition.
3 = High
mA output will fail to its
high
condition.
Содержание QUANTUM3
Страница 1: ...QUANTUM 3 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 14: ...Page 6 EU Declaration of Conformity ...
Страница 17: ...Page 9 The full dimensions of the enclosure are as shown below ...
Страница 21: ...Page 13 ...
Страница 22: ...Page 14 ...
Страница 48: ...Page 40 This page left blank intentionally ...