Page
139
Failsafe
P808 Fail-safe Mode
By default, if a fail-safe condition occurs, then the display, relays and the mA
output are held at their last
known
values until a valid reading is obtained. If
required, then you can change this so that the unit goes to
high
(100% of
span), or
low
(empty) as follows:
Option
Description
1 = Known
Remain at the last
known
value
2 = High
Will fail to the
high
value (100% of Span).
3= Low
Will fail to the
low
value (empty)
See Also P218, P228, P238, P248, P258, P268 Relay Fail-safe and P840 mA Output Fail-safe
Important Information
In the event of a
fail-safe
condition occurring, the display, relays and mA
Output can be configured to fail to a condition which is independent of each
other. To set independent
Relay Failsafe
see
P218, 228, 238, 248, 258, 268
.
And for independent
mA Output Failsafe
see
P840.
P809 Fail-safe Time
In the event of a fail-safe condition occurring the fail safe timer determines
the time before fail-safe mode is activated.
Default = 2 mins
.
If the timer activates, the unit goes into
fail-safe
, as determined by
P808
,
(
Display
),
P218, 228, 238, 248, 258, 268
, (
Relays
) and
P840
(
mA Output
).
When this happens, you will see the message “
Failed Safe
!” on the display,
along with a message explaining why (lost echo or transducer fault, for
example)
When a valid measurement is obtained then the display, relays and mA output
will be restored and the timer is reset.
Содержание QUANTUM3
Страница 1: ...QUANTUM 3 INSTRUCTION MANUAL ...
Страница 2: ......
Страница 4: ......
Страница 14: ...Page 6 EU Declaration of Conformity ...
Страница 17: ...Page 9 The full dimensions of the enclosure are as shown below ...
Страница 21: ...Page 13 ...
Страница 22: ...Page 14 ...
Страница 48: ...Page 40 This page left blank intentionally ...