Страница 3: ... circuit described herein Every effort has been made to ensure accuracy of this documentation but Pulsar Process Measurement Limited cannot be held liable for any errors Pulsar Process Measurement Limited operates a policy of constant development and improvement and reserve the right to amend technical details as necessary The Quantum3 unit shown on the cover of this manual is used for illustrativ...

Страница 4: ......

Страница 5: ...ocation 16 Preparation for Operation 18 Maintenance 18 Chapter 3 How To Use Your Quantum3 Pump Controller 19 Operating the Controls 19 Display 19 Run Mode 20 Program Mode 21 How to Access Program Mode 21 Hot Keys 22 Menu Keys 23 Numeric Keys 23 Test Mode 26 Using the RS232 Serial Interface 27 Parameter Defaults 28 Factory Defaults 28 Chapter 4 Quick Set up Guide 29 Quick Setup Menu 31 Example 1 Le...

Страница 6: ... Time 91 Common Parameters 94 Pump Trips 94 Pump Advanced Parameters 96 Pump Run On 96 Starting 96 Stopping 97 Pump Exercising 97 Wall Cling 98 Storm 98 Rate Method 99 FlowPulse 99 Derived Flow 99 Digital Inputs 100 About Digital Inputs 100 Common Parameters Set up 100 Input Type 100 Input Function 101 Device Fail 102 Duty 103 Override 106 Reset 106 Digital Input Parameters 106 Common Par 106 Digi...

Страница 7: ...t 2 Parameters 146 mA2 Range 146 mA2 Operation 146 mA2 Setpoint 147 mA2 Limits 147 mA2 Trim 148 mA2 Failsafe 148 Compensation Parameters 149 Offset 149 Temperature 149 OVF Persist 149 Velocity 150 Stability Parameters 150 Damping 150 Indicator 150 Rate 150 Filters 151 Echo Processing Parameters 152 Transducer Status 152 DATEM Parameters 154 System Parameters 155 Passcode 155 Backup 155 System Info...

Страница 8: ...Test Parameters 165 Simulation 165 Hardware 167 Chapter 6 Troubleshooting 169 Chapter 7 Disposal 171 Parameter Record 172 ...

Страница 9: ...erating manual will ensure that your installation is as simple as possible About this Manual It is important that this manual is referred to for correct installation and operation There are various parts of the manual that offer additional help or information as shown Tips TIP At various parts of this manual you will find tips to help you Additional Information Additional Information At various pa...

Страница 10: ... pump and level control routines suitable for an extremely wide variety of applications Easy calibration and maintenance free fit and forget performance mean that you can install the Quantum3 pump controller rapidly and with confidence Ten user definable relays with adjustable individual on and off points Seven user definable digital inputs 2 x isolated mA output RS 232 and intelligent performance...

Страница 11: ...her control equipment In addition the digital inputs can be used to modify pump and control regimes in order to optimise performance There are two isolated 4 20 mA outputs that can be connected to a chart recorder or PLC to monitor level space distance or pumping rate independently from that shown on the display There is an RS232 port so that the Quantum3 can be operated remotely by a PC or other ...

Страница 12: ...ge or 2 mm whichever is greater Max range Dependant on transducer maximum 40m dB40 Min range Dependent upon transducer minimum zero dB Mach 3 Rate response Fully adjustable Echo Processing Description DATEM Digital Adaptive Tracking of Echo Movement Outputs Analogue output 2 off Isolated floating outputs to 150V of 4 20 mA or 0 20 mA into 500 user programmable and adjustable 0 1 resolution Digital...

Страница 13: ...eypad PC programming via RS232 Programming security Via passcode user selectable and adjustable Programmed data integrity Via non volatile RAM plus backup Supply Power supply 85 264V AC 50 60Hz DC 22 28V 25W maximum power Fuses 2A T 20mm fuse Pulsar Process Measurement Limited operates a policy of constant development and improvement and reserve the right to amend technical details as necessary ...

Страница 14: ...Page 6 EU Declaration of Conformity ...

Страница 15: ... The AC is 85 264V AC 50 60Hz The DC is 22 28V Location All electronic products are susceptible to electrostatic shock so follow proper grounding procedures during installation The Quantum3 Pump Controller and FlowPulse must be mounted in a non hazardous safe area and the transducer can be fitted in a hazardous area ...

Страница 16: ...ardous area For a clear view of the LCD display it is recommended that you mount it at eye level The mounting surface is vibration free The ambient temperature is between 20ºC and 50ºC There should be no high voltage cables or inverters close by Dimensions The Quantum3 should be installed by cutting a hole in the panel as detailed below ...

Страница 17: ...Page 9 The full dimensions of the enclosure are as shown below ...

Страница 18: ...dance with the installation instructions contained in the Transducer User Guide Wire the transducer to the Quantum3 transducer terminals as follows Transducer Terminal Connection Details Red Power White Signal Black 0 volts Green Screen 32 31 30 30 When using 2 core screened extension cable the Black and Green wires of the transducer should be connected to the screen of the extension cable which i...

Страница 19: ...e 1 applications a transducer certified to FM Class I Div 1 Group A B C D ClassII Div 1 Group E F G Class III is used and must be supplied via a 1500A breaking fuse which is fitted as standard to the Quantum3 Restrictions do not use in the presence of these groups of Chemicals Aliphatic Hydro Carbons Ketones or Esters For EEx ia I S a transducer certified to FM Class I Div 1 Group A B C D ClassII ...

Страница 20: ...hieved in FlowPulse via the termination switch If termination is required at the Quantum3 fit the included 120R resistor across terminals 34 35 The spurs to the FlowPulses should be kept as short as possible Wiring detail Description Quantum3 Flow Pulse 1 Flow Pulse 2 Flow Pulse 3 Flow Pulse 4 Flow Pulse Power 24VDC 25 1 1 1 1 0V 24 2 2 2 2 FlowPulse comms 34 9 9 9 9 FlowPulse comms 35 10 10 10 10...

Страница 21: ...Page 13 ...

Страница 22: ...Page 14 ...

Страница 23: ...loating mA outputs to 150 V of 4 20mA or 0 20mA and the load should not exceed 500 Digital Inputs Where the Quantum3 is required to provide power for a Device Input the appropriate Digital Input should be wired between the 24VDC supply terminal and the IN terminal TOTAL maximum current available for all seven digital inputs from the 24VDC supply is 24mA When Device Inputs are self powered connecti...

Страница 24: ...Page 16 Fuse Location The mains fuse is located under the removable cover at the bottom of the unit as illustrated below ...

Страница 25: ...necting cables must be adequately insulated in accordance with local regulations Strip back 30 mm of the outer insulation of the cable Strip 5 mm of insulation from the end of each conductor Twist all exposed strands of the conductor together Insert the stripped conductor into the terminal block as far as it will go and tighten the terminal block screw Ensure that all strands are firmly clamped in...

Страница 26: ...the equipment wipe with a damp cloth Do not use any solvents on the enclosure or front panel Important Information The unique DATEM software comes into operation as soon as power is applied and is designed to monitor a moving level or target with the transducer in a fixed position If after any period of use it should become necessary to move the transducer for any reason from its original operatin...

Страница 27: ...of measure along with status messages with regards to the Transducer Echo reception and Fail Safe Mode Additionally it can be programmed to provide status messages on alarms pumps etc When in the Program Mode the display is used to read information on the Menu System Parameter Number and parameter details and values which can be entered During Test Mode the display is used to monitor the simulated...

Страница 28: ...us of optional remote PC connection 5 Bargraph display gives visual indication of measurement in of span 6 Level indicators Run Mode indicates in which direction the level is moving Program Mode indicates at which level of the menu system you are currently at There are two main operating modes for your Quantum3 Run Mode and Program Mode There is also a Test Mode used for checking the set up All mo...

Страница 29: ...tering a value for each of the parameters that are relevant to your application provides all the programming information How to Access Program Mode To enter program mode you simply enter the passcode via the keypad followed by the ENTER key The default passcode is 1997 so you would press the following Note There is a time out period of 15 minutes when in program mode after which time run mode will...

Страница 30: ...vidual pump running hours Not used with Quantum3 Displays echo confidence echo strength H A L L average noise peak noise or temperature Not used with Quantum3 Total number of pump starts and individual pump starts Reset parameter to default setting Instantaneous mA output Not used with Quantum3 Dependant on application displays Distance Level Space Volume or rate of change of level Toggle relay se...

Страница 31: ...ate the level moving up and down 1 Used to confirm each action for example select a menu option or when entering a parameter number or value 2 Used to confirm questions asked by your Quantum3 such as before restoring factory defaults Used to navigate up a level in the menu system and back to run mode Used to cancel a value entered in error Numeric Keys These keys are used for entering numerical in...

Страница 32: ...n into the sub menu you can scroll round using the arrow keys and press ENTER to go to the required section of parameters Once you have reached the relevant section scroll through the parameters and enter the necessary information To enter the information use the numeric keys and press ENTER when you will see the message Saved If you press CANCEL then the change you made will not be saved and the ...

Страница 33: ...n either the menu or sub menu level by pressing a numeric key you can enter the parameter number directly and jump straight there You cannot type a parameter number whilst at parameter level only at one of the two menu levels When you are at a parameter the text line rotates automatically displaying the parameter name number the applicable units and the maximum and minimum figure you can enter The...

Страница 34: ...ter simulation first go to program mode Then using the menu system select menu item Test then sub menu item Simulation Simply change the value of the parameter P980 to one of the following 1 Manual soft simulation 2 Automatic soft simulation 3 Manual hard simulation 4 Automatic hard simulation To return to program mode press CANCEL and test mode will end When in manual simulation by default test m...

Страница 35: ...cepted or NO if it is not To log on you send the command ACCESS pppp where pppp is the passcode P922 To log off you send the command ACCESS OFF To read a parameter value send the command Pxxx where xxx is the parameter you wish to read and the unit will respond with the parameter value To set a parameter send the command Pxxx yy where xxx is the parameter number and yy is the value you wish to set...

Страница 36: ... All relays are set OFF The date P931 and time P932 in the Quantum3 were set at the factory but may need checking and amending if for example the application is in a time zone other than GMT see Chapter 5 Parameter Guide for full details TIP In some applications it is simplest to empty the vessel take a reading from the Quantum3 for distance and then setup the empty level to this figure Once you a...

Страница 37: ...first item on the menu system Try pressing the two arrow keys to see some more menu options but return to Quick Setup and press This takes you to the common applications parameter P200 This takes you to the common applications parameters and you will see some options appearing on the display Note If you have already setup a common application then there will be a number shown other than 0 and you ...

Страница 38: ...mp duty and any requirement for alarms and choose the appropriate options If you want to set up a pump up reservoir control application then choose 3 You then need to decide the number of pumps required the pump duty and any requirement for alarms and choose the appropriate options In certain cases the Quick Setup Menu has been customised for particular customer specific applications to choose one...

Страница 39: ...elay 1 2 Set to Relay 2 3 Set to Relay 3 4 Set to Relay 4 5 Set to Relay 5 6 Set to Relay 6 7 Set to Relay 7 8 Set to Relay 8 9 Set to Relay 9 0 Set to Relay 10 How Many Alarms 0 No Alarms 1 One Alarm 2 Two Alarm 3 Three Alarm 4 Four Alarm 5 Five Alarm 6 Six Alarms 7 Seven Alarms 8 Eight Alarms 9 Nine Alarms 10 Ten Alarms List will be truncated according to the number of pumps selected For Each Al...

Страница 40: ...row key to scroll through them but if you want to view or change each one just press ENTER Parameter Default Description P101 Transducer 2 dB6 Type of transducer being used P104 Measurement Units 1 metres Select units to be used for programming measurement information P105 Empty Level 6 m Distance from the face of the transducer to the material at the bottom of the vessel P106 Span 5 7 m Distance ...

Страница 41: ...tables below Either Alarm or Level control Depends on application P243 P244 Relay 4 ON OFF setpoints Factory preset as a to appropriate level according to the span already entered See tables below Either Alarm or Level control Depends on application P253 P254 Relay 5 ON OFF setpoints Factory preset as a to appropriate level according to the span already entered See tables below Either Alarm or Pum...

Страница 42: ...Pump Number On Setpoint Off Setpoint Pump Down One Pump 1 50 20 Pump Down Two Pump 1 Pump 2 50 70 20 20 Pump Down Three Pump 1 Pump 2 Pump 3 50 60 70 20 20 20 Pump Down Four Pump 1 Pump 2 Pump 3 Pump 4 40 50 60 70 20 20 20 20 Pump Down Five Pump 1 Pump 2 Pump 3 Pump 4 Pump 5 40 50 60 70 75 20 20 20 20 20 Pump Down Six Pump 1 Pump 2 Pump 3 Pump 4 Pump 5 Pump 6 40 50 60 70 75 80 20 20 20 20 20 20 ...

Страница 43: ... Pump 3 50 40 30 80 80 80 Pump Up Four Pump 1 Pump 2 Pump 3 Pump 4 60 50 40 30 80 80 80 80 Pump Up Five Pump 1 Pump 2 Pump 3 Pump 4 Pump 5 60 50 40 30 25 80 80 80 80 80 Pump Up Six Pump 1 Pump 2 Pump 3 Pump 4 Pump 5 Pump 6 60 50 40 30 25 20 80 80 80 80 80 80 Relay Function Relay I D On Setpoint Off Setpoint Alarm HiHi 90 85 Alarm High 85 80 Alarm Low 10 15 Alarm LoLo 5 10 ...

Страница 44: ... 38m 80 high alarm off P214 2 24m 15 low alarm off P224 0 42m 10 low alarm on P223 0 28m 0 empty level In this example when the level rises to 2 38 m relay 1 will come on until the level drops to 2 24 m when it will turn off If the level drops to 0 28 m then relay 2 will come on until it rises 0 42 m when it will turn off The display will show the level in the tank The mA output will be representa...

Страница 45: ...ducer P101 2 dB6 Material P102 1 Liquid Measnt Units P104 1 metres Empty Level P105 3 5 metres Span P106 2 8 metres Programming is now complete and the unit can be returned to the run mode press CANCEL until Run Mode Is displayed on the LCD press ENTER and the Quantum3 will return to the Run Mode Note If relay setpoints do not meet the exact requirements of the application they can be modified to ...

Страница 46: ... 2 to Relay 2 and the high level alarm to Relay 5 This will operate as follows During normal operation pump 1 will come on at 1 4 m and pump down to 0 56 m The setpoints are then shifted to pump 2 which will come on first next time During peak periods when pump 1 cannot cope pump 1 will come on at 1 4 m pump 2 will come on at 1 96 m and pump down to 0 56 m The setpoints are then shifted to pump 2 ...

Страница 47: ...igh Alarm Alarm No 1 5 Set Relay 5 Xducer P101 2 dB6 Measnt Units P104 1 metres Empty Level P105 3 5 metres Span P106 2 8 metres Programming is now complete and the unit can be returned to the run mode press CANCEL until Run Mode Is displayed on the LCD press ENTER and the Quantum3 will return to the Run Mode Note If relay setpoints do not meet the exact requirements of the application they can be...

Страница 48: ...Page 40 This page left blank intentionally ...

Страница 49: ... Diagrams Shown below is a set of charts to show you how all the various parts can be found using the menu system Top Level Menu Quick Setup Application Relays Pump Advanced Digital Inputs FS Backup Data Logs Display mA Output 1 Efficiency FlowPulse Compensation Stability System Test Device Comm Echo Processing mA Output 2 Volume Tariff Guard ...

Страница 50: ...Page 42 Application Menu Operation Distances P100 Mode P101 Transducer P104 Measurement Units P102 Material P105 Empty Level P106 Span P107 Near Blanking P108 Far Blanking ...

Страница 51: ...82 Rly 9 P292 Alarm ID or Pump Group Rly 2 P223 Rly 3 P233 Rly 4 P243 Rly 5 P253 Rly 6 P263 Rly 7 P273 Rly 8 P283 Rly 9 P293 Relay Setpoint 1 Rly 2 P224 Rly 3 P234 Rly 4 P244 Rly 5 P254 Rly 6 P264 Rly 7 P274 Rly 8 P284 Rly 9 P294 Relay Setpoint 2 Rly 2 P225 Rly 3 P235 Rly 4 P245 Rly 5 P255 Rly 6 P265 Rly 7 P275 Rly 8 P285 Rly 9 P295 Relay Setpoint 3 as required Rly 2 P227 Rly 3 P237 Rly 4 P247 Rly...

Страница 52: ...Prime Level P350 Run Interval P351 Run Duration Starting P352 Start Delay P353 Power Delay Exercise P354 Exercise Enable P355 Idle Time P356 Exercise Time P357 Minimum Head Storm P370 Pump Disable P371 Disable Time Rate Method P116 Rate Calc When P118 1 Derived P117 RMA Delay P118 Output Flow ...

Страница 53: ...Filter P306 Override Level P372 Type P373 Function P374 Assign Input 2 P375 Input 3 P378 Input 4 P381 Input 5 P384 Input 6 P387 Type Digital Input 2 to Digital Input 6 Input 2 P376 Input 3 P379 Input 4 P382 Input 5 P385 Input 6 P388 Function Input 2 P377 Input 3 P380 Input 4 P383 Input 5 P386 Input 6 P389 Assign Digital Input 7 P390 Type P391 Function P392 Assign ...

Страница 54: ...pe P334 Function P335 Forced Level Input 2 P336 Input 3 P339 Input 4 P342 Input 5 P345 Type Digital Input 2 to Digital Input 5 Input 2 P337 Input 3 P340 Input 4 P343 Input 5 P346 Function Input 2 P338 Input 3 P341 Input 4 P344 Input 5 P347 Forced Level Digital Input 6 P363 Type P364 Function P365 Forced Level ...

Страница 55: ...4 P421 PT5 P427 PT6 P433 PT7 P439 PT8 P446 PT9 P451 PT2 P410 PT3 P416 PT4 P422 PT5 P428 PT6 P434 PT7 P440 PT8 P447 PT9 P452 PT2 P411 PT3 P417 PT4 P423 PT5 P429 PT6 P435 PT7 P441 PT8 P448 PT9 P453 P393 Enable P394 Lead Time P395 Lag Time P396 Minimum Pump Time P398 Overflow Level P400 PT1 Day P401 PT1 Week P402 PT1 Start Peak Date P403 PT1 End Peak Date P404 PT1 Start Time P405 PT1 End Time P454 PT...

Страница 56: ...6 Total Dates 2 to 9 P463 465 467 469 471 473 475 477 Totals 2 to 9 P478 Vol Date 10 P580 Min Temp P479 Volume 10 P581 Min Temp Date P582 Min Temp Time P583 Max Temp P584 Max Temp Date P585 Max Temp Time P586 Current Temperature P510 Pump 1 Hours P512 Pump 1 Starts per Hour P513 Pump 1 Run On P564 Pump 10 Hours P565 Pump 6 Starts P566 Pump 10 Starts per Hour P567 Pump 10 Run On P514 Pump 1 Draw P5...

Страница 57: ...ation P1171 Allocation P1191 Allocation P1132 Diameter P1152 Diameter P1172 Diameter P1192 Diameter P1133 Pipe Type P1153 Pipe Type P1173 Pipe Type P1193 Pipe Type P1134 Density P1154 Density P1174 Density P1194 Density P1135 Damping P1155 Damping P1175 Damping P1195 Damping P1137 MagThreshold P1157 MagThreshold P1177 MagThreshold P1197 MagThreshold P1138 SR Mode P1158 SR Mode P1178 SR Mode P1198 ...

Страница 58: ...ume Units P606 Correct Factor P607 Max Volume P612 614 616 618 620 622 624 626 628 630 632 634 636 638 640 642 644 646 648 650 652 654 656 658 660 662 664 666 668 670 Level Bkpts 2 to 31 Breakpoints P610 Level Bkpt 1 P611 Vol Bkpt 1 P613 615 617 619 621 623 625 627 629 631 633 635 637 639 641 643 645 647 649 651 653 655 657 659 661 663 665 667 669 671 Vol Bkpts 2 to 31 P672 Level Bkpt 32 P673 Vol ...

Страница 59: ...Page 51 Efficiency Menu Set Up P187 Pump Effic P188 Calib Delay P189 Cal Duration P190 Persist Cnt P191 Demote Pumps P192 Demote Flags P193 Calib Pumps ...

Страница 60: ... Decimal Places P804 Display Conversion P808 Fail Mode P809 Fail Time P810 Units P811 Alarms P812 Pumps P813 Control P814 Misc P816 Totaliser R P817 Auxiliary Offset Totaliser P820 Totaliser P821 Totaliser R P822 Totaliser Decimal P823 Totaliser Multiplier P800 Display Units ...

Страница 61: ...P836 Low Limit P835 High Value P837 High Limit P838 Low mA Trim P839 High mA Trim P840 Fail Mode Range P830 mA Out Range Range P890 mA2 Out Range Operation Setpoint Limits Trim Fail Safe P891 mA2 Out Mode P892 Low Value P894 Low Limit P893 High Value P895 High Limit P896 Low mA Trim P897 High mA Trim P898 Fail Mode ...

Страница 62: ...e P854 Fixed Temperature P860 Sound Velocity OVF Count P865 OVF Count Damping Indicator Rate Filters P870 Fill Damping P871 Empty Damping P872 Fill Indicator P873 Empty Indicator P874 Rate Update P875 Rate Time P876 Rate Distance P877 Rate Value P878 Lower Cutoff P880 Gate Mode P881 Fixed Distance P884 Peak Percent ...

Страница 63: ...Page 55 Echo Processing Menu Xdr 1 Status P900 Xdr 1 Status P901 Echo Confidence 1 P902 Echo Strength 1 P903 Average Noise 1 P904 Peak Noise 1 P905 Sensitivity 1 P906 Side Clearance 1 ...

Страница 64: ...ff Colour P970 DST Enable P922 Passcode P927 Hardware Revision P928 Serial Number P929 Site Ident P930 Factory Default P931 Time P932 Date Format P936 Alarm Colour P937 Pump Colour P938 Control Colour P939 Misc Colour P971 DST Difference P972 DST Start Time P973 Start Day P974 Start Week P975 Start Month P976 DST End Time P977 End Day P978 End Week P979 End Month ...

Страница 65: ...f Comms Type PROFIBUS P061 Comms Baud P130 Device Mode P131 Protocol P132 Device Address P133 Device Baud P134 Parity P135 Stop Bit P136 Data Format P137 Delay milliseconds P132 Device Address P143 Address Lock P144 Call Type P145 Tel No 1 P146 Tel No 2 P147 Tel No 3 P148 Timed Out P149 Retry No ...

Страница 66: ...est Menu Simulation Hardware P980 Simulate P981 Increment P982 Rate P983 Start Level P984 Incremental Change P990 Self Test P991 Hardware Test P992 mA Out Test P994 Transducer Test P995 Keys Test P996 Relay Test ...

Страница 67: ... of the following Option Description 0 Auxiliary Use the mA input device 1 dB3 Transducer is a dB3 Range 0 125 to 3 00 metres 2 dB6 Default Transducer is a dB6 Range 0 3 to 6 00 metres 3 dB10 Transducer is a dB10 Range 0 3 to 10 00 metres 4 dB15 Transducer is a dB15 Range 0 5 to 15 00 metres 5 dB25 Transducer is a dB25 Range 0 6 to 25 00 metres 6 dB40 Transducer is a dB40 Range 1 2 to 40 00 metres...

Страница 68: ...ption 1 metres Default All units of measure are METRES 2 cm All units of measure are CENTIMETRES 3 mm All units of measure are MILLIMETRES 4 feet All units of measure are FEET 5 inches All units of measure are INCHES P105 Empty Level This parameter is to be set to the maximum distance from the face of the transducer to the empty point in P104 Measurement Units Note this value affects span as well ...

Страница 69: ...vel P105 less the Near Blanking distance P107 when you set the empty level P107 Near Blanking Distance This parameter sets the distance from the face of the transducer that is not measurable and is pre set to the minimum value dependant on the Xducer P101 selected It should not be set to less than this figure but can be increased typically to ignore close in obstructions Transducer Near Blanking D...

Страница 70: ...mpty point that the unit will be able to measure and by default is pre set to 20 of the empty level If the surface being monitored can extend beyond the Empty Level P105 then the far blanking distance can be increased to a maximum of 100 of empty level This parameter is always entered as a of empty level ...

Страница 71: ... parameters for Relay 5 26 parameters for Relay 6 27 parameters for Relay 7 28 parameters for Relay 8 29 parameters for Relay 9 57 parameters for Relay 10 The third digit is parameter specific and is the same for each relay resulting in the following parameter numbers for each relay Relay 1 210 to 219 Relay 2 220 to 229 Relay 3 230 to 239 Relay 4 240 to 249 Relay 5 250 to 259 Relay 6 260 to 269 Re...

Страница 72: ...alarm is raised if the power fails to the unit 2 Pump Relay is programmed as a pump relay which will energise to switch the pump ON and de energise to switch the pump OFF 3 Control Relay is programmed as a control relay which will energise to switch ON and de energise to switch OFF 4 Miscellaneous Relay is programmed as a miscellaneous relay which will energise to switch ON and de energise to swit...

Страница 73: ...vel in the vessel and the type of rate of change alarm P212 222 232 242 252 262 272 282 292 572 and two setpoints must be set P213 223 233 243 253 263 273 283 293 573 P214 224 234 243 253 263 273 283 293 573 Setpoints are entered in Display Units per minute or of span per minute and a negative value should be entered for a Rate Alarm on a de creasing level and a positive value for an increasing le...

Страница 74: ...53 263 273 283 293 573 Reset Level P214 224 234 254 264 274 284 294 574 High Alarm Level P215 225 235 245 255 265 275 285 295 575 All level Setpoints are entered in Display Units or of span as referenced to Empty Level Time to Overflow P219 229 239 249 259 269 279 289 579 Setpoint entered in minutes 10 RMA Alarm Alarm is based on the rate of change of level during a pumping cycle and on the type o...

Страница 75: ...ype or identification the relay should respond to as follows Alarm ID Description Setpoints 1 General Default Relay goes ON when the value rises to the ON setpoint and goes OFF when the value lowers to the OFF setpoint P213 223 233 243 253 263 273 283 293 573 is ON Setpoint P214 224 234 244 254 264 274 284 294 574 is OFF Setpoint 2 High Relay goes ON when the value rises to the ON setpoint and goe...

Страница 76: ... different identifier 6 In bounds Relay goes ON if value is inside the zone between the two setpoints Relay Setpoints P213 223 233 243 253 263 273 283 293 573 and P214 224 234 244 254 264 274 284 294 574 Setpoints can be set in any order as the unit knows that you are setting an in bounds alarm 7 Out of bounds Relay goes ON if value is outside the zone between the two setpoints Relay Setpoints P21...

Страница 77: ...ll not operate 1 Relay 1 Alarm is assigned to pump on Relay 1 2 Relay 2 Alarm is assigned to pump on Relay 2 3 Relay 3 Alarm is assigned to pump on Relay 3 4 Relay 4 Alarm is assigned to pump on Relay 4 5 Relay 5 Alarm is assigned to pump on Relay 5 6 Relay 6 Alarm is assigned to pump on Relay 6 7 Relay 7 Alarm is assigned to pump on Relay 7 8 Relay 8 Alarm is assigned to pump on Relay 8 9 Relay 9...

Страница 78: ... failure is detected on relay 4 None 5 Fail Rel 5 Relay goes ON when a device failure is detected on relay 5 None 6 Fail Rel 6 Relay goes ON when a device failure is detected on relay 6 None 7 Fail Rel 7 Relay goes ON when a device failure is detected on relay 7 None 8 Fail Rel 8 Relay goes ON when a device failure is detected on relay 8 None 9 Fail Rel 9 Relay goes ON when a device failure is det...

Страница 79: ...p 2 Relay goes ON when a fail signal is detected on digital input 2 None 3 Fail Inp 3 Relay goes ON when a fail signal is detected on digital input 3 None 4 Fail Inp 4 Relay goes ON when a fail signal is detected on digital input 4 None 5 Fail Inp 5 Relay goes ON when a fail signal is detected on digital input 5 None 6 Fail Inp 6 Relay goes ON when a fail signal is detected on digital input 6 None...

Страница 80: ...te is above than the Alarm setpoint for longer than the Persistence Time provided the level is above the Prime Head and goes OFF when the pumping rate lowers below the Alarm setpoint for longer than the Persistence Time P213 223 233 243 253 263 273 283 293 573 is Alarm Setpoint P214 224 234 244 254 264 274 284 294 574 is Persistence Time P215 225 235 245 255 265 275 285 295 575 is Prime Head 3 NRV...

Страница 81: ... provided the level is above the Prime Head and goes OFF when the pumping rate lowers below the Alarm setpoint for longer than the Persistence Time P213 223 233 243 253 263 273 283 293 573 is Alarm Setpoint P214 224 234 244 254 264 274 284 294 574 is Persistence Time P215 225 235 245 255 265 275 285 295 575 is Prime Head ...

Страница 82: ... P264 P274 P284 P294 P574 Relay Setpoint 2 Determines the ON or OFF point for the alarm according to the ID selected Important Information Setpoints are entered in values according to the function selected Level entered in Display Units or of span as referenced to Empty Level Rate of Change entered in Display Units per minute or of span per minute For an alarm on an increasing level enter setpoint...

Страница 83: ...el has to be below of fall below before an activated alarm can be considered to be deactivated provided the time to overflow does not exceed the Time to Overflow P219 229 238 249 259 269 279 289 299 579 and the level is below the Reset Level the alarm will turn OFF P215 P225 P235 P245 P255 P265 P275 P285 P295 P575 Relay Setpoint 3 This parameter determines the level at which the High Alarm will be...

Страница 84: ...4 P234 P244 P254 P264 P274 P284 P294 P574 Relay Setpoint 2 This parameter determines the Persistence Time This is the amount of time the rate has to persist above below the Alarm Setpoint P213 223 233 243 253 263 273 283 293 573 before the alarm will change state It is used to prevent relay chatter if the rate is near the alarm setpoint Units are in Seconds P215 P225 P235 P245 P255 P265 P275 P285 ...

Страница 85: ...ime and each pump has its own setpoints P213 223 233 243 253 263 273 283 293 573 P214 224 234 244 254 264 274 284 294 574 2 Fixed duty backup If a pump fails to meet the demand due to malfunction intake blockage etc then it is stopped and another pump shall take over Each pump has its own setpoints P213 223 233 243 253 263 273 283 293 573 P214 224 234 244 254 264 274 284 294 574 3 Alternate duty a...

Страница 86: ...ts are sequentially rotated between the pumps to ensure equal pump use 5 Duty backup and assist First pump comes on if it cannot cope it goes off and next pump comes on duty backup This continues until the last pump comes on and if it cannot cope the first pump comes back on to assist the last pump duty assist if the level continues to rise all other pumps will come on assist in turn until the lev...

Страница 87: ...ice ratio set to 2 and 1 respectively then pump A will operate for twice as many hours as pump B 7 Service ratio duty backup If a pump fails to meet the demand due to malfunction intake blockage and so on then it is stopped and another pump shall take over Each time a pump is required to start then the pump with the least running hours with respect to the service ratio is started i e the setpoints...

Страница 88: ...ir start up sequence with each other If the two pumps cannot keep up the level rises to the setpoints of the other two pumps which take over and rotate their sequence with each other Important Information The pumps are started and stopped at the ON and OFF setpoints To pump down reduce level then set ON higher than OFF To pump up increase level then set ON lower than OFF The third parameter for ea...

Страница 89: ...meter will determine the service ratio that will be used to switch the pump when pump duty selected is a Service Ratio duty P211 221 231 241 251 261 271 281 291 571 6 7 or 9 Service ratio P215 P225 P235 P245 P255 P265 P275 P285 P295 P575 Relay Setpoint 3 This parameter determines the Service Ratio in values of See the appropriate pump duty function table P211 221 231 241 251 261 271 281 291 571 fo...

Страница 90: ...s or flush valve operation Options Description 0 Off Default Relay is always de energised 1 Time Relay will energise ON after the Cycle time that is set in Relay Setpoint 2 P214 224 234 244 254 264 274 284 294 574 And turns OFF de energises after the On Time Period that is set in Relay Setpoint 1 P213 223 233 243 253 263 273 283 293 573 2 Storm Relay will energise ON when storm conditions are in e...

Страница 91: ...ush relay Alarm ID P212 222 232 242 252 262 272 282 292 572 is used to enter the relay number to which the assigned pump is connected Flush Valve Pump relay requires three setpoints The first set point P213 223 233 243 253 263 273 283 293 573 determines the Flush Interval which is the number of main pump cycles that should occur before the Flush Valve Pump operates The second setpoint P214 224 234...

Страница 92: ...3 293 573 determines the level at which the relay is to be activated N B level setpoint for open relay increase the level must be lower than the setpoint for the close relay decrease the level The relay will energise ON after the Limit time that is set in Relay Setpoint 3 P215 225 235 245 255 265 275 285 295 575 And turns OFF de energises after the Drive Period that is set in Relay Setpoint 2 P214...

Страница 93: ...1 1 2 3 or 6 This parameter has no function and will not be displayed P211 221 231 241 251 261 271 281 291 571 4 Flush Valve If the relay is selected for Flush Valve Pump then this parameter is used to determine to which pump the Flush function is assigned Enter the relay number to which the assigned pump is connected P211 221 231 241 251 261 271 281 291 571 5 Step Time If the relay is selected fo...

Страница 94: ...221 231 241 251 261 271 281 291 571 for further information P211 221 231 241 251 261 271 281 291 571 3 Aeration Relay Setpoint 1 is entered in Minutes to set Cycle Time See the appropriate relay Function tables P211 221 231 241 251 261 271 281 291 571 for further information P211 221 231 241 251 261 271 281 291 571 4 Flush Valve Relay Setpoint 1 is entered in Pump cycles to set Flush Interval See ...

Страница 95: ...ts are entered in Minutes to set Time Period that the relay will remain ON See the appropriate relay Function tables P211 221 231 241 251 261 271 281 291 571 for further information P211 221 231 241 251 261 271 281 291 571 4 Flush Valve Relay Setpoints are entered in cycles to set the number of Flush cycles See the appropriate relay Function tables P211 221 231 241 251 261 271 281 291 571 for furt...

Страница 96: ...1 241 251 261 271 281 291 571 4 Flush Valve Enter desired Flush duration in seconds See the appropriate relay Function tables P211 221 231 241 251 261 271 281 291 571 for further information P211 221 231 241 251 261 271 281 291 571 5 Step Time This parameter is used to determine the Limit Time between each Drive Period Relay Setpoints are entered in Minutes during which time the relay will remain ...

Страница 97: ... as set in Relay Setpoint 1 P213 223 233 243 253 263 273 283 293 573 And turns OFF de energises after the specified On Time period as set in Relay Setpoint 2 P214 224 234 244 254 264 274 284 294 574 2 Totaliser Relay will energise ON momentarily each time the specified flow has passed as set in Relay setpoint 1 P213 223 233 243 253 263 273 283 293 573 this parameter sets the multiplication factor ...

Страница 98: ...23 P233 P243 P253 P263 P273 P283 P293 P573 Relay Setpoint 1 Relay Setpoints are entered in Hours Minutes HH MM to set Time at which relay will energise Default 00 00 HH MM P214 P224 P234 P244 P254 P264 P274 P284 P294 P574 Relay Setpoint 2 Relay Setpoints are entered in Minutes to set Time Period that the relay will remain ON Default 0 00 mins P211 221 231 241 251 261 271 281 291 571 2 Totaliser P2...

Страница 99: ...ault Relay is always de energised 1 Fixed duty assist All pumps are used to assist each other run at the same time and each pump has its own setpoints P213 223 233 243 253 263 273 283 293 573 P214 224 234 244 254 264 274 284 294 574 2 Fixed duty backup If a pump fails to meet the demand due to malfunction intake blockage etc then it is stopped and another pump shall take over Each pump has its own...

Страница 100: ...backup This continues until the last pump comes on and if it cannot cope the first pump comes back on to assist the last pump duty assist if the level continues to rise all other pumps will come on assist in turn until the level decreases to the pump off points Each pump has its own setpoints P213 223 233 243 253 263 273 283 293 573 P214 224 234 244 254 264 274 284 294 574 Important Information Th...

Страница 101: ... P283 P293 P573 Relay Setpoint 1 This parameter determines the ON point of the pump P214 P224 P234 P244 P254 P264 P274 P284 P294 P574 Relay Setpoint 2 This parameter determines the OFF point for the pump When a relay is being used for a pump by time function then the sixth parameter will determine the maximum time the pump will be allowed to run before it is switched off and the next pump takes ov...

Страница 102: ...n in its current state 2 De energise Relay will De energise 3 Energise Relay will Energise Pump Trips When using digital inputs to monitor pump running status and assign relays to Pump Reset this function allows for a pre programmed number of pump fails P307 Trip limit to be automatically reset before putting a pump out of service A pump fail is defined as the change of state of the trip signal fr...

Страница 103: ...tempts P300 without completing a successful pump cycle that pump will be put out of service and will not be rest until such time that the fail condition is removed P307 Trip Limit This parameter sets the maximum number of pump fails allowed in any 24 hour rolling period P308 Reset Interval This parameter sets the cooling off period prior to a Reset Pulse being initiated P309 Reset Pulse This param...

Страница 104: ...red time period in hours at which pump run on should occur P351 Run Duration This parameter sets the length of time in seconds that pumps will run on for it should be noted that only one run on is allowed per Run Interval Starting This feature is used to reduce the effects of power surges caused by switching of pumps in the following instances P352 Power surge mains or hydraulic that is generated ...

Страница 105: ...se time P356 providing a Minimum head level P357 is present and all other pumps are switched off P354 Exercise Enable This parameter determines if Pump Exercising is enabled or disabled Option Description 0 No Default Pump Exercising disabled 1 Yes Pump Exercising enabled P355 Idle Time Sets the Idle Time to elapse before Pump Exercising is to be activated Set the required time period in minutes D...

Страница 106: ... in metres Storm This facility enables all pumps to be disabled P370 during a storm condition to prevent the futile running or potential damage due to the continued use of pumps during flood conditions Provision is also made to allow a maximum time period P371 for which pumps will remain disabled during such conditions For this function to operate a relay must have been assigned to Storm and have ...

Страница 107: ... Derived Derived flow calculates the flow Changing this parameter changes the method the Quantum3 uses for its source for flow rate The default for the Quantum3 is FlowPulse FlowPulse FlowPulse is an ultrasonic non invasive flow monitor that supplies the Quantum3 with real time flow Using FlowPulse eliminates the need to calculate the inflow rates meaning that changes in to inflow with not affect ...

Страница 108: ...l Input 7 P390 to 392 Common Parameters Set up These parameters determine specific operational criteria for particular digital input functions and are common to each digital input Input Type The digital inputs can be either voltage source where Quantum3 will supply the switching voltage or voltage synch where the switching voltage is supplied by the input from the device for full details see Chapt...

Страница 109: ...to be in its operational status until the expiry of P304 Input Delay which is used to determine the delay time that occurs from the time that the device is called to run and the digital input providing a signal appropriate to its operational status 2 Duty input will provide a signal to manually select the lead device 3 Override ON input will provide a signal to override all selected pump setpoints...

Страница 110: ...med to operate on Relay 1 Pump 2 is connected and programmed to operate on Relay 2 Pump 1 Fail signal is connected to Digital Input 1 Pump 2 Fail signal is connected to Digital Input 2 Each digital input has to be assigned to the device relay output that it relates to this is determined by Assignment P374 377 380 383 386 389 392 In the case of our example Digital Input 1 will be assigned to Relay ...

Страница 111: ...ts have been programmed as detailed in Using the Relays earlier in this chapter The signals providing details on the lead or duty pump status are connected to the digital inputs as described in Chapter 2 Installation and the input Type P372 375 378 381 384 387 390 is configured as detailed in Input Type earlier in this chapter Pump 1 is connected and programmed to operate on Relay 1 Pump 2 is conn...

Страница 112: ...mp 2 then the pump connected to Relay 2 will assume the role of lead duty pump regardless of the settings programmed in the Quantum3 When the level rises to the ON Setpoint for the first pump the relay 2 will energise and Pump 2 will start in the normal manner If the level continues to rise then relay 1 will energise and Pump 1 will start in accordance with the settings programmed for pump 2 Binar...

Страница 113: ...n Input Type earlier in this chapter Pump 1 is connected and programmed to operate on Relay 1 Pump 2 is connected and programmed to operate on Relay 2 Duty Input 1 signal is connected to Digital Input 3 Duty Input 2 signal is connected to Digital Input 4 When no signals are present on either Digital Input 3 or Digital Input 4 then devices will run in the auto mode as determined by the Quantum3 in ...

Страница 114: ... on this input will Reset all Device Fail signals to the no fault condition When using this function the unit will check all inputs for such conditions so there is no requirement to assign the input to a specific relay output Alternatively the key has been allocated as a Hot Key which when pressed will give details of any Device Fail and provides prompts to Reset any failures to the no fault condi...

Страница 115: ...em immediately after the expiry of the Override Delay dependent on the selected Digital Input Function P373 376 379 382 385 388 391 3 Override ON or 4 Override OFF and providing the level is above the Min Override P303 when Override ON is selected Enter the required delay time in minutes P303 Min Override Determines the minimum level required before an Override Delay P302 will be in effect when Di...

Страница 116: ...time in seconds P306 Override Level This parameter will determine which pumps setpoints will be overridden when Digital Input Function P373 376 379 382 385 388 391 3 Override ON Only pumps with normal ON setpoints below the Override Level will be activated when an Override ON condition exists and that the Override Delay P302 and Min Override P303 where required have been satisfied Enter the requir...

Страница 117: ...nput 1 6 Digital input is used to Fail put out of service a device connected to the relay specified in P374 377 380 383 386 389 392 Assignment 2 Duty Digital input is used to select the device pump connected to the relay specified in P374 377 380 383 386 389 392 Assignment as the current duty device pump 3 Override ON Digital input is used to provide a signal to activate an Override ON condition o...

Страница 118: ...ssigned to Device connected to Relay 2 3 Relay 3 Digital input is assigned to Device connected to Relay 3 4 Relay 4 Digital input is assigned to Device connected to Relay 4 5 Relay 5 Digital input is assigned to Device connected to Relay 5 6 Relay 6 Digital input is assigned to Device connected to Relay 6 7 Relay 7 Digital input is assigned to Device connected to Relay 7 8 Relay 8 Digital input is...

Страница 119: ...ion Description 0 Off default Float Switch Backup is not used 1 Always Backup will be active continuously and will respond to an input from a Backup device at all times 2 On Xdr Fail Backup will only be active at times when the unit has gone into a Failsafe mode P330 Input Filter This parameter can be used to ignore spurious changes of state on the digital inputs and determines the time that a cha...

Страница 120: ... duty pump to the lowest pump Off level If after the Lag Time has expired the pump has not reached its Off point it will continue to pump until the Off point is reached On expiry of the Lag Time all pumps will assume their normal operation and will be switched On and Off according to their respective setpoints Enter desired time in minutes P396 Min Pump Run This parameter determines the minimum am...

Страница 121: ...Time not in effect 1 Every Peak Time will be in effect everyday 2 Monday Peak Time will be in effect on Monday 3 Tuesday Peak Time will be in effect on Tuesday 4 Wednesday Peak Time will be in effect on Wednesday 5 Thursday Peak Time will be in effect on Thursday 6 Friday Peak Time will be in effect on Friday 7 Saturday Peak Time will be in effect on Saturday 8 Sunday Peak Time will be in effect o...

Страница 122: ... Pk This parameter sets the date on which the Peak Time will end Enter the desired End Date in DD MM format P404 410 416 422 428 434 440 446 452 458 PT1 Start This parameter sets the time at which the Peak Time will start Enter the desired Start Time in HH MM format P405 411 417 423 429 435 441 447 453 459 PT1 End This parameter sets the time at which the Peak Time will end Enter the desired End T...

Страница 123: ...to be cleared to factory default values Important Information In order to ensure the accuracy of pumped Volume during a 24 hour period the Time P932 must be set correctly And if required enable Daylight Saving for the appropriate time difference P970 P979 Temperature The following parameters give information on temperature conditions seen by the Temperature source P852 in ºC All of these parameter...

Страница 124: ...tored total for any reason e g a replacement pump being fitted P511 Pump 1 Starts This parameter displays the current total pump starts for Pump 1 Any value from 0 9999 can be entered to facilitate any update to the stored total for any reason e g a replacement pump being fitted P512 Pump 1 Starts Hour This parameter displays the current pump Starts Hour for Pump 1 Any value from 0 9999 can be ent...

Страница 125: ... same information as above for Pump 2 P522 P527 Pump 3 These parameters contain the same information as above for Pump 3 P528 P533 Pump 4 These parameters contain the same information as above for Pump 4 P534 P539 Pump 5 These parameters contain the same information as above for Pump 5 P540 P545 Pump 6 These parameters contain the same information as above for Pump 6 P546 P551 Pump 7 These paramet...

Страница 126: ...ceptional repeatability Up to 4 FlowPulse units can be used with Quantum3 to give control and monitoring based on real time flow The Quantum3 allows the connected FlowPulse units to be allocated to either pump main outlet all or to just monitor the flow in a pipe For the purpose of totalising and outputting flow via the mA output a single flow value must be obtained This flow value will either be ...

Страница 127: ...In configuration 1 the FlowPulse attacked to the Rising Main should be allocated as an All FlowPulse P1131 P1151 P1171 P1191 This will ensure that this FlowPulse is the only one used to totalise and output flow ...

Страница 128: ...iguration 2 each of the FlowPulse will be allocated to the pumps they are attached to Without a FlowPulse allocated to All the summation of flow being measured by all FlowPulse will be used to totalise and output flow ...

Страница 129: ... each pump and a FlowPulse attached to the Rising Main allocated to All In this situation although there are FlowPulse attached to the pumps the FlowPulse attached to the Rising Main and allocated to All will be used as the output for flow and totalising ...

Страница 130: ...r the pipes they are monitoring When returning to Run Mode after being in Program Mode the parameters of all Flow Pulses are updated Each FlowPulse connected to the Quantum3 needs to have a unique slave address all supplied FlowPulse are pre set to 126 this can be changed using FlowPulse PC software This address must then be set in the Quantum3 To set the Quantum3 so that flow being measured by ea...

Страница 131: ...ns 6 Mil USG Flow will be measured in Mil USG P1111 Time Units This parameter determines the time units the flow is measured by when displaying the flow outputted by each FlowPulse Option Description 1 Per Second Default Flow will be measured in seconds 2 Per Minute Flow will be measured in minutes 3 Per Hour Flow will be measured in hours 4 Per Day Flow will be measured in days P1112 Flow Decimal...

Страница 132: ...sed to monitor the flow on either an individual pump the main outlet or just monitor a pipe with flow Option Description 0 None Default The FlowPulse is not allocated to anything 1 Relay 1 The FlowPulse is allocated to Relay 1 2 Relay 2 The FlowPulse is allocated to Relay 2 3 Relay 3 The FlowPulse is allocated to Relay 3 4 Relay 4 The FlowPulse is allocated to Relay 4 5 Relay 5 The FlowPulse is al...

Страница 133: ...wPulse is allocated to Option Description 0 Very Low The Liquid has a Very Low density 1 Low The Liquid has a Low density 2 Medium The Liquid has a Medium density 3 High The Liquid has a High density 4 Very High The Liquid has a Very High density P1135 P1155 P1175 P1195 Damping Damping is used to set how quickly you wish the FlowPulse to respond to changes in fluctuations in flow speed Minimum 10 ...

Страница 134: ...e The higher the step response threshold the larger the jump in flow needs to be before damping is skipped P1140 P1160 P1180 P1200 Track Method This parameter sets the flow tracking method of the FlowPulse Magnitude forces the tracking to go to the first point in which the flow reaches 5 of the noise floor Gradient will force the tracking to go to the first point in which the gradient of the trace...

Страница 135: ...efore the current day P1143 P1163 P1183 P1203 Totaliser 3 These are read only parameters that display the total flow measured by the FlowPulses two days before the current day P1144 P1164 P1184 P1204 Totaliser 4 These are read only parameters that display the total flow measured by the FlowPulses three days before the current day P1145 P1165 P1185 P1205 Totaliser 5 These are read only parameters t...

Страница 136: ...low back or turbulence before calculating the Inflow Rate This parameter is also used in the RMA Alarm function to allow the pumping rate to settle after starting the first pump Enter desired time in minutes Default 1 minute Enter desired time in minutes P207 Inflow Method This parameter determines which method is used to calculate the inflow of material during a pump down cycle Option Description...

Страница 137: ...d by the vessel manufacturer or you can create one based on the dimensions of the vessel You can enter up to 32 pairs of breakpoints and the more you enter the greater accuracy of the volume calculation will be Conversion P600 Vessel Shape This parameter determines which vessel shape is used when utilising Volume Conversion The choices are as shown in the table below along with the dimensions that...

Страница 138: ...tangular Flat sloped base Width and Breadth of rectangular section and height of bottom P600 8 Horizontal cylinder with flat ends Cylinder diameter and tank length P600 9 Horizontal cylinder with parabolic ends Cylinder diameter length of one end section and tank length P600 10 Sphere Sphere diameter P600 11 Universal Linear No dimensions required level and volume breakpoints used P600 12 Universa...

Страница 139: ...abola base Height of base Cylinder Diameter P600 5 Cylindrical Half sphere base Cylinder Diameter P600 6 Cylindrical Flat sloped base Height of base Cylinder Diameter P600 7 Rectangular Flat sloped base Height of base Width of rectangle Breadth of rectangle P600 8 Horizontal cylinder flat ends Length of Cylinder Cylinder Diameter P600 9 Horiz Cyl parabolic ends Length of Cylinder Cylinder Diameter...

Страница 140: ...al so that the volume calculated is relative to the actual amount of material that can be contained between empty level P105 and 100 of span P106 Default 1 P607 Max Volume This parameter displays the actual maximum volume that has been calculated by the Quantum3 i e P604 Calculated Volume x P606 Correction Factor and is a Read Only parameter The volume displayed will be shown in P605 Volume Units ...

Страница 141: ...here the section is slightly curved mostly linear but has got a small arc You can enter any number of pairs between 2 and 32 Universal Curved P600 12 This volume calculation creates a curved approximation of the level volume relationship and works best if the vessel is non linear and there are no sharp angles Level Volume You should enter 2 level volume breakpoints at the minimum and maximum level...

Страница 142: ...Up P187 Pump Eff This parameter determines whether pump efficiency is enabled or disabled Option Description 0 Off Default Pump efficiency is disabled 1 On Pump efficiency is enabled P188 Calib Delay This parameter is used to set a delay after all pumps have stopped to allow for any turbulence of the material surface to settle prior to monitoring the level in the vessel and determining the inflow ...

Страница 143: ...mp will be allowed to run at the reduced efficiency before the alarm will be activated The Persist Count can be set to Min 0 Max 99 Default 6 P191 Demote Pumps When an efficiency alarm is being used this parameter will determine if a pump is to be demoted to the last pump in the duty cycle on activation of the alarm When Demote Pump is enabled and the efficiency alarm is activated after the predet...

Страница 144: ... Pump 1 2 4 6 12 Pump 3 4 44 Pump 3 4 6 13 Pump 1 3 4 45 Pump 1 3 4 6 14 Pump 2 3 4 46 Pump 2 3 4 6 15 Pump 1 2 3 4 47 Pump 1 2 3 4 6 16 Pump 5 48 Pump 5 6 17 Pump 1 5 49 Pump 1 5 6 18 Pump 2 5 50 Pump 2 5 6 19 Pump 1 2 5 51 Pump 1 2 5 6 20 Pump 3 5 52 Pump 3 5 6 21 Pump 1 3 5 53 Pump 1 3 5 6 22 Pump 2 3 5 54 Pump 2 3 5 6 23 Pump 1 2 3 5 55 Pump 1 2 3 5 6 24 Pump 4 5 56 Pump 4 5 6 25 Pump 1 4 5 57...

Страница 145: ... counted down time to the pump start Once the pump has started the display will show a countdown time equal to the Cal Duration P189 calculation of pump efficiency will be completed on the expiry of the count and the unit will return to normal operation If you choose to calibrate the pumps automatically Option 7 then when the unit is returned to the RUN mode each pump will be calibrated in turn as...

Страница 146: ...r example you wanted to reference the reading to sea level where you would enter the distance between Empty Level P105 and sea level If the empty level point is below sea level then enter a negative value P804 Display Conversion The reading is multiplied by the value of this parameter before being displayed The default is 1 0 but if for example you wanted to display the reading in yards then set t...

Страница 147: ... occurring the display relays and mA Output can be configured to fail to a condition which is independent of each other To set independent Relay Failsafe see P218 228 238 248 258 268 And for independent mA Output Failsafe see P840 P809 Fail safe Time In the event of a fail safe condition occurring the fail safe timer determines the time before fail safe mode is activated Default 2 mins If the time...

Страница 148: ...ion 0 No Default Alarm messages will not be displayed 1 Yes Alarm messages will be displayed P812 Pumps Messages This parameter determines whether notification messages are displayed on the auxiliary line of the display in run mode when a pump relay is switched on or off The message is in the form Pump 1 ON where the number displayed is the number of the relay Option Description 0 No Default Pump ...

Страница 149: ... measurement When using and RMA alarm it can also be used to display the pumping rate The options are as follows Option Description 0 Off Default Auxiliary display not used to display levels 2 Xducer 1 Displays level from Xducer 1 4 Rate Displays Inflow I and pumping rate P P816 Totalisier R This parameter determines whether or not the resettable totaliser will be displayed in the auxiliary line o...

Страница 150: ...or small amount enter the factor by which the actual flow rate is multiplied by before incrementing the totaliser E g if flowrate is being calculated and displayed in ltrs second and it is desired to increment the totaliser in cubic metres select 7 1000 When viewing the totaliser display will state Units are L 1000 and the totaliser will be incremented every 1000 litres Options are Option Descript...

Страница 151: ...ely proportional to the mA mode P831 so if the reading is 0 the output is 20mA If the reading is 100 the output is 0mA 4 20 to 4 mA mA output inversely proportional to the mA mode P831 so if the reading is 0 the output is 20mA If the reading is 100 the output is 4mA Operation P831 mA Mode This parameter determines how the mA Output relates to what is measured By default it operates exactly the sam...

Страница 152: ...P831 at which the low mA output will occur 0 or 4mA dependant on P830 mA Range Default 0 000m P835 mA High Level This parameter sets in Measurement Units P104 the value of level distance or space depending on the selected mA Out Mode P831 at which the high mA output will occur 20mA Default 6 000m Limits P836 mA Low Limit This parameter sets the lowest value that the mA output will drop to the defa...

Страница 153: ... it using this parameter You can either type in the offset directly or use the arrow keys to move the output up and down until you get the expected result reading on the remote device that is connected Failsafe P840 mA Fail safe Mode This parameter determines what happens to the mA output in the event of the unit going into fail safe mode The default is to do the same as the system fail safe P808 ...

Страница 154: ...ely proportional to the mA mode P891 so if the reading is 0 the output is 20mA If the reading is 100 the output is 0mA 4 20 to 4 mA mA output inversely proportional to the mA mode P891 so if the reading is 0 the output is 20mA If the reading is 100 the output is 4mA mA2 Operation P891 mA2 Out Mode This parameter determines how the mA Output relates to what is measured By default it operates exactl...

Страница 155: ...891 at which the low mA output will occur 0 or 4mA dependant on P890 mA Range Default 0 000m P893 mA2 High Level This parameter sets in Measurement Units P104 the value of level distance or space depending on the selected mA Out Mode P891 at which the high mA output will occur 20mA Default 6 000m mA2 Limits P894 mA2 Low Limit This parameter sets the lowest value that the mA output will drop to the...

Страница 156: ... it using this parameter You can either type in the offset directly or use the arrow keys to move the output up and down until you get the expected result reading on the remote device that is connected mA2 Failsafe P898 mA2 Fail safe Mode This parameter determines what happens to the mA output in the event of the unit going into fail safe mode The default is to do the same as the system fail safe ...

Страница 157: ...ansducer If for any reason no temperature input is received then the Fixed Temp value is used as set by P854 The temperature source can be specifically set as follows Option Description 1 Automatic Will automatically select transducer temperature sensor if available or fixed temperature P854 if no temperature sensor found 2 Xducer 1 Always uses temperature reading from transducer 3 Fixed Always us...

Страница 158: ...te Default 10m min P871 Empty Damping This parameter determines the maximum rate at which the unit will respond to a decrease in level It should be set slightly higher than the maximum vessel empty rate Default 10m min Indicator P872 Fill Indicator This parameter determines the rate at which the LCD fill indicator activates Default 10m min P873 Empty Indicator This parameter determines the rate at...

Страница 159: ...y P878 Lower Cutoff This parameter is used to select the minimum Rate to be calculated and can be used to eliminate unwanted updates from effects of ripples waves on the surface of the material Filters The following parameters can be used to filter out unwanted changes of level caused by a rippled or agitated surface P881Fixed Distance This parameter determines the width of gate to be used in trac...

Страница 160: ... It is useful to help find the best mounting location for the transducer where you should aim to get the highest figure It is a percentage of confidence that the echo reporting the level is the correct one P902 Echo Strength This parameter displays the most recent echo strength figure for the transducer where a higher figure indicates a better returned echo P903 Average Noise This is the mean nois...

Страница 161: ...ions It is recommended that this parameter not be changed unless necessary as any echo below the DATEM will be ignored Default 5dB 50mV P906 Side Clearance This parameter sets the distance by which the DATEM trace will be separated from the raw echo when the DATEM trace covers an echo returned from an undesired obstruction Default 0 05m ...

Страница 162: ...nge taken and all echo returns referenced out 2 Default DATEM trace will assume its default value 3 Def Reset Default DATEM to factory settings 4 Set Min DATEM When set DATEM levels at this point will be accepted as a minimum P021 Set Distance Allows the user or service personnel to determine which echo is to be displayed On start up if the unit displays an incorrect reading then simply enter the ...

Страница 163: ... P925 Parameter Backup Restore This parameter is used to make a backup of all parameters for example to ensure a default set is maintained within the unit If alterations are made to the parameters that do not work as intended then the backup set can be restored into the unit You can make two separate backup copies if you wish called backup 1 and backup 2 and restore from either The options are Opt...

Страница 164: ...it It is read only and cannot be changed The Serial Number can also be checked whilst in RUN Mode by pressing the decimal point key P929 Site Identification This parameter allows you to give each unit an individual reference number for identification purposes You can set any number between 1 and 99999 P930 Factory Defaults This parameter resets all parameter values to the original Factory Set valu...

Страница 165: ...ED Colour Each relay has an associated LED located on the unit s front panel which indicates the status of the relay By default the LED of any relay that has been programmed but is in its OFF state will be illuminated yellow When ON alarm relays will cause the LED to illuminate Red and pump control and miscellaneous relays will cause the LED to illuminate green LED s of any relays that have not be...

Страница 166: ...he relay has been failed but not put out of service After the maximum attempts P300 have been made to start the device relay and it is put out of service then the relay LED will remain lit on red until such time that the input is reset Watchdog You can check how many times the unit has been switched on and look at the date and time of the last ten starts This can be useful if there have been power...

Страница 167: ...e correct operation of Daylight Saving Time P932 Time should be checked and adjusted if necessary to ensure that it is set for the current valid time P970 DST Enable When Enabled set to 1 the internal clock will be automatically adjusted to compensate for the difference between standard time and Daylight Saving Time Default 1 Yes P971 DST Difference This parameter sets the time difference between ...

Страница 168: ... Sunday Default DST will start on a Sunday P974 Start Week This parameter will determine the week of the month P975 in which Daylight Saving Time is to start Option Description 1 Week 1 DST will start on day P973 in the first week P974 of the month P975 2 Week 2 DST will start on day P973 in the second week P974 of the month P975 3 Week 3 DST will start on day P973 in the third week P974 of the mo...

Страница 169: ...start during the month of September 10 October DST will start during the month of October 11 November DST will start during the month of November 12 December DST will start during the month of December P976 DST End Time This parameter is used to set the time of day at which Daylight Saving Time will end the time is entered in the format HH MM 24 hour format Default 02 00 P977 End Day Use this para...

Страница 170: ...9 P979 End Month This parameter is used to select the month in which Daylight Saving Time will end Option Description 1 January DST will end during the month of January 2 February DST will end during the month of February 3 March DST will end during the month of March 4 April DST will end during the month of April 5 May DST will end during the month of May 6 June DST will end during the month of J...

Страница 171: ...es a specific alarm point as determined by the setting of the relay s the unit will dial and connect to a remote telephone number to provide details of the event P144 Call Type This parameter determines what type of connection is made via the modem Option Description 0 Off Default Remote alarm function is disabled 1 Ring This option initiates a connection to a remote modem computer which will then...

Страница 172: ... to enter the next 6 digits following the 0 s of the telephone number to be dialled If there are less than 6 digits following the 0 s then just enter the digits required if there are more digits following the 0 s then enter the first 6 digits and then proceed to P147 and enter the remaining digits P147 Tel No3 This parameter is used to enter any remaining digits of the telephone number to be diall...

Страница 173: ...down between empty level or the pre determined Start Level P983 and Pump Control relay switch points if you wish to change the direction of the level movement e g to go beyond relay setpoints this can be done by using the arrow keys In manual simulation using the arrow keys will allow you to move the level up and down as required The choices for you to enter are as follows 1 Manual soft simulation...

Страница 174: ... Rate P982 To decrease the rate at which the level moves decrease the Increment P981 or increase the Rate P982 P983 Start Level When using automatic simulation this parameter can be used to pre determine the point at which the simulated level will start at and return to This can be used to simulate the lowest point to which the level would normally operate P984 Inc Change When using automatic simu...

Страница 175: ...s on the LCD are lit up so you can see if they all work Press ENTER to end the test The LED s all go green at the same time Keys You should press each key to confirm it works with a counter showing how many more keys you have to press Be sure to press the CANCEL key last as this will show if all keys were pressed or not If they were not then an error message is displayed P992 mA Out Test This para...

Страница 176: ...hould press each key to confirm it works with a counter showing how many more keys you have to press Press the CANCEL key last as this will confirm if all keys were pressed or not If they were not then an error message is displayed ...

Страница 177: ...surface of material Enter Program Mode and directly access P21 Set Distance type in the measured distance press ENTER and ENTER again when prompted wait until SET is displayed and return to Run Mode display will now update to the correct reading Material level is consistently incorrect by the same amount Check empty level P105 display offset P802 and measurement offset P851 LED s change colour at ...

Страница 178: ...oblem with the communications between the FlowPulse s in question this will require someone to make sure the FlowPulse s are connected correctly The second is that a parameter or more is not being sent to the FlowPulse correctly This could be coursed by entering in a value that the FlowPulse doesn t except such as a pipe diameter that the specific FlowPulse cannot except as it is too large ...

Страница 179: ...ble and Transducer in accordance with regional environmental regulations for electrical electronic products Controllers Remove power disconnect the Controller and remove battery if fitted Dispose of Controller in accordance with regional environmental regulations for electrical electronic products Dispose of batteries in accordance with regional environmental regulations for batteries EU WEEE Dire...

Страница 180: ...on Default 1 2 3 4 5 P100 Mode 1 Dist P101 Xducer 2 dB6 P102 Material 1 Liquid Distances Parameter Details Entered Values No Description Default 1 2 3 4 5 P104 Measurement Units 1 metres P105 Empty Level 6 000 metres P106 Span 5 700 metres P107 Near Blanking 0 300 metres P108 Far Blanking 20 0 ...

Страница 181: ...ues No Description Default 1 2 3 4 5 P220 R2 Type 0 Off P221 R2 Function 0 Off P222 R2 Alarm ID Pump Group 1 Off P223 R2 Set 1 0 000 metres P224 R2 Set 2 0 000 metres P225 R2 Set 3 0 000 P227 R2 Closures 0 P228 R2 Fail Safe 0 P229 R2 Max Rate 0 000 metres Relay 3 Parameter Details Entered Values No Description Default 1 2 3 4 5 P230 R3 Type 0 Off P231 R3 Function 0 Off P232 R3Alarm ID Pump Group 1...

Страница 182: ...No Description Default 1 2 3 4 5 P250 R5 Type 0 Off P251 R5 Function 0 Off P252 R5 Alarm ID Pump Group 1 Off P253 R5 Set 1 0 000 metres P254 R5 Set 2 0 000 metres P255 R5 Set 3 0 000 P257 R5 Closures 0 P258 R5 Fail Safe 0 P259 R5 Max Rate 0 000 metres Relay 6 Parameter Details Entered Values No Description Default 1 2 3 4 5 P260 R6 Type 0 Off P261 R6 Function 0 Off P262 R6 Alarm ID Pump Group 1 Of...

Страница 183: ...No Description Default 1 2 3 4 5 P280 R8 Type 0 Off P281 R8 Function 0 Off P282 R8 Alarm ID Pump Group 1 Off P283 R8 Set 1 0 000 metres P284 R8 Set 2 0 000 metres P285 R8 Set 3 0 000 P287 R8 Closures 0 P288 R8 Fail Safe 0 P289 R8 Max Rate 0 000 metres Relay 9 Parameter Details Entered Values No Description Default 1 2 3 4 5 P290 R9 Type 0 Off P291 R9 Function 0 Off P292 R9 Alarm ID Pump Group 1 Of...

Страница 184: ...R10 Fail Safe 0 P579 R10 Max Rate 0 000 metres Pump Trips Parameter Details Entered Values No Description Default 1 2 3 4 5 P307 Trip Limit 0 P308 Reset Interval 10 mins P309 Reset Pulse 3 secs P310 Pump 1 Trip Read Only P311 Pump 2 Trip Read Only P312 Pump 3 Trip Read Only P313 Pump 4 Trip Read Only P314 Pump 5 Trip Read Only P315 Pump 6 Trip Read Only P316 Pump 7 Trip Read Only P317 Pump 8 Trip ...

Страница 185: ... Default 1 2 3 4 5 P348 Stop Delay 0 0 secs Exercise Parameter Details Entered Values No Description Default 1 2 3 4 5 P354 Exercise Enable 0 No P355 Idle Time 720 00 mins P356 Exercise Time 30 0 secs P357 Minimum Head 0 0 metres Wall Cling Parameter Details Entered Values No Description Default 1 2 3 4 5 P360 Wall Cling 0 00 metres Storm Parameter Details Entered Values No Description Default 1 2...

Страница 186: ...scription Default 1 2 3 4 5 P372 Type 1 Input N C P373 Function 1 DeviceFail P374 Assignment 0 None Dig Input 2 Parameter Details Entered Values No Description Default 1 2 3 4 5 P375 Type 1 Input N C P376 Function 1 DeviceFail P377 Assignment 0 None Dig Input 3 Parameter Details Entered Values No Description Default 1 2 3 4 5 P378 Type 1 Input N C P379 Function 1 DeviceFail P380 Assignment 0 None ...

Страница 187: ...eviceFail P386 Assignment 0 None Dig Input 6 Parameter Details Entered Values No Description Default 1 2 3 4 5 P387 Type 1 Input N C P388 Function 1 DeviceFail P389 Assignment 0 None Dig Input 7 Parameter Details Entered Values No Description Default 1 2 3 4 5 P390 Type 2 Input N O P391 Function 5 Reset P392 Assignment 0 None ...

Страница 188: ...n 0 Off P335 Forced Level 0 1 metres Dig Input 2 Parameter Details Entered Values No Description Default 1 2 3 4 5 P336 Type 1 Input N C P337 Function 0 Off P338 Forced Level 0 1 metres Dig Input 3 Parameter Details Entered Values No Description Default 1 2 3 4 5 P339 Type 1 Input N C P340 Function 0 Off P341 Forced Level 0 1 metres Dig Input 4 Parameter Details Entered Values No Description Defau...

Страница 189: ...02 PT 1 Start Peak Date 01 01 P403 PT 1 End Peak Date 31 12 P404 PT 1 Start Time 00 00 P405 PT 1 End Time 00 00 Peak Time 2 Parameter Details Entered Values No Description Default 1 2 3 4 5 P406 P581 PT 2 Day 0 P407 PT 2 Week 6 P408 PT 2 Start Peak Date 01 01 P409 PT 2 End Peak Date 31 12 P410 PT 2 Start Time 00 00 P411 PT 2 End Time 00 00 Peak Time 3 Parameter Details Entered Values No Descriptio...

Страница 190: ...5 Start Peak Date 01 01 P427 PT 5 End Peak Date 31 12 P428 PT 5 Start Time 00 00 P429 PT 5 End Time 00 00 Peak Time 6 Parameter Details Entered Values No Description Default 1 2 3 4 5 P430 P581 PT 6 Day 0 P431 PT 6 Week 6 P432 PT 6 Start Peak Date 01 01 P433 PT 6 End Peak Date 31 12 P434 PT 6 Start Time 00 00 P435 PT 6 End Time 00 00 Peak Time 7 Parameter Details Entered Values No Description Defa...

Страница 191: ...arameter Details Entered Values No Description Default 1 2 3 4 5 P448 P581 PT 9 Day 0 P449 PT 9 Week 6 P450 PT 9 Start Peak Date 01 01 P451 PT 9 End Peak Date 31 12 P452 PT 9 Start Time 00 00 P453 PT 9 End Time 00 00 Peak Time 10 Parameter Details Entered Values No Description Default 1 2 3 4 5 P454 P581 PT 10 Day 0 P455 PT 10 Week 6 P456 PT 10 Start Peak Date 01 01 P457 PT 10 End Peak Date 31 12 ...

Страница 192: ...lume 6 P472 Vol Date 7 P473 Volume 7 P474 Vol Date 8 P475 Volume 8 P476 Vol Date 9 P477 Volume 9 P478 Vol Date 10 P479 Volume 10 P480 Clear Logs Temperature Parameter Details Entered Values No Description Default 1 2 3 4 5 P580 P581 Minimum Temperature Read Only P581 Min Temperature Date Read Only P582 Min Temperature Time Read Only P583 Maximum Temperature Read Only P584 Max Temperature Date Read...

Страница 193: ... 0 0 hours P517 P2 Starts 0 P518 P2 Starts Hour 0 P519 P2 Run On s 0 P520 P2 Draw 0 P521 P2 Efficiency 0 Pump 3 Parameter Details Entered Values No Description Default 1 2 3 4 5 P522 P3 Hours 0 0 hours P523 P3 Starts 0 P524 P3 Starts Hour 0 P525 P3 Run On s 0 P526 P3 Draw 0 P527 P3 Efficiency 0 Pump 4 Parameter Details Entered Values No Description Default 1 2 3 4 5 P528 P4 Hours 0 0 hours P529 P4...

Страница 194: ... Draw 0 P545 P6 Efficiency 0 Pump 7 Parameter Details Entered Values No Description Default 1 2 3 4 5 P546 P7 Hours 0 0 hours P547 P7 Starts 0 P548 P7 Starts Hour 7Parameter Details Entered Values No Description Default 1 2 3 4 5 P551 P581 P5 Hours 0 0 hours P552 P5 Starts 0 P553 P5 Starts Hour 0 P554 P5 Run On s 0 0 P549 P7 Run On s 0 P550 P7 Draw 0 P551 P7 Efficiency 0 Pump 8 Parameter Details E...

Страница 195: ...s 0 P553 P5 Starts Hour 0 P554 P5 Run On s 0 0 P561 P9 Run On s 0 P562 P9 Draw 0 P563 P9 Efficiency 0 Pump 10 Parameter Details Entered Values No Description Default 1 2 3 4 5 P564 P10 Hours 0 0 hours P565 P10 Starts 0 P566 P10 Starts Hour Parameter Details Entered Values No Description Default 1 2 3 4 5 P551 P581 P5 Hours 0 0 hours P552 P5 Starts 0 P553 P5 Starts Hour 0 P554 P5 Run On s 0 0 P567 ...

Страница 196: ...1 Setup Parameter Details Entered Values No Description Default 1 2 3 4 5 P1130 P581 Address 126 P1131 Allocation 0 None P1132 Diameter 1 0 015m P1133 Pipe Type 0 Cast Iron P1134 Density 2 Medium P1135 Damping 24 P1137 MagThreshold 1600 P1138 SR Mode 1 Yes P1139 SR Threshold 60 P1140 Track Method 0 Auto P1141 Totaliser1 0 P1142 Totaliser2 0 P1143 Totaliser3 0 P1144 Totaliser4 0 P1145 Totaliser5 0 ...

Страница 197: ...hod 0 Auto P1161 Totaliser1 0 P1162 Totaliser2 0 P1163 Totaliser3 0 P1164 Totaliser4 0 P1165 Totaliser5 0 FP3 Setup Parameter Details Entered Values No Description Default 1 2 3 4 5 P1170 P581 Address 126 P1171 Allocation 0 None P1172 Diameter 1 0 015m P1173 Pipe Type 0 Cast Iron P1174 Density 2 Medium P1175 Damping 24 P1177 MagThreshold 1600 P1178 SR Mode 1 Yes P1179 SR Threshold 60 P1180 Track M...

Страница 198: ...2 Totaliser2 0 P1203 Totaliser3 0 P1204 Totaliser4 0 P1205 Totaliser5 0 VOLUME Set up Parameter Details Entered Values No Description Default 1 2 3 4 5 P205 P581 Pump Volume Enable 0 P206 Settle Time 1 00 min P207 Inflow Method 1 Conversion Parameter Details Entered Values No Description Default 1 2 3 4 5 P600 P581 Vessel Shape 0 P601 Dim 1 As required 0 000 P602 Dim 2 As required 0 000 P603 Dim 3...

Страница 199: ... P625 Volume Breakpoint 8 0 00 P626 Level Breakpoint 9 0 00 P627 Volume Breakpoint 9 0 00 P628 Level Breakpoint 10 0 00 P629 Volume Breakpoint 10 0 00 P630 Level Breakpoint 11 0 00 P631 Volume Breakpoint 11 0 00 P632 Level Breakpoint 12 0 00 P633 Volume Breakpoint 12 0 00 P634 Level Breakpoint 13 0 00 P635 Volume Breakpoint 13 0 00 P636 Level Breakpoint 14 0 00 P637 Volume Breakpoint 14 0 00 P638 ...

Страница 200: ...kpoint 28 0 00 P665 Volume Breakpoint 28 0 00 P666 Level Breakpoint 29 0 00 P667 Volume Breakpoint 29 0 00 P668 Level Breakpoint 30 0 00 P669 Volume Breakpoint 30 0 00 P670 Level Breakpoint 31 0 00 P671 Volume Breakpoint 31 0 00 P672 Level Breakpoint 32 0 00 P673 Volume Breakpoint 32 0 00 Tables Parameter Details Entered Values No Description Default 1 2 3 4 5 P696 Reset Breakpoints 0 P697 Number ...

Страница 201: ...ult 1 2 3 4 5 P808 P581 Fail Mode 1 Known P809 Fail Time 2 0 mins Auxiliary Parameter Details Entered Values No Description Default 1 2 3 4 5 P810 Units 1 Yes P811 Alarms 0 No P812 Pumps 0 No P813 Control 0 No P814 Miscellaneous 0 No P816 Totaliser R 0 No P817 Auxiliary Offset 0 000 metres Totaliser Parameter Details Entered Values No Description Default 1 2 3 4 5 P820 Totaliser Tot 0 00 P821 Tota...

Страница 202: ...ls Entered Values No Description Default 1 2 3 4 5 P834 Low Level 0 000 metres P835 P581 High Level 5 700 metres Limits Parameter Details Entered Values No Description Default 1 2 3 4 5 P836 Low Limit 0 00 mA P837 P581 High Limit 20 00 mA Trim Parameter Details Entered Values No Description Default 1 2 3 4 5 P838 Low Trim 0 00 mA P839 P581 High Trim 0 00 mA Fail Safe Parameter Details Entered Valu...

Страница 203: ...ls Entered Values No Description Default 1 2 3 4 5 P892 Low Level 0 000 metres P893 P581 High Level 5 700 metres mA2 Limits Parameter Details Entered Values No Description Default 1 2 3 4 5 P894 Low Limit 0 00 mA P895 P581 High Limit 20 00 mA mA2 Trim Parameter Details Entered Values No Description Default 1 2 3 4 5 P896 Low Trim 0 00 mA P897 P581 High Trim 0 00 mA mA2 Fail Safe Parameter Details ...

Страница 204: ...0 OVF Persist Parameter Details Entered Values No Description Default 1 2 3 4 5 P865 OVF Count 10 STABILITY Damping Parameter Details Entered Values No Description Default 1 2 3 4 5 P870 Fill Damping 10 0000 P871 Empty Damping 10 0000 Indicator Parameter Details Entered Values No Description Default 1 2 3 4 5 P872 Fill Indicator 10 0000 P873 Empty Indicator 10 0000 Rate Parameter Details Entered V...

Страница 205: ...Average Noise Read Only P904 Peak Noise Read Only P905 Sensitivity 5 0 dB P906 Side Clearance 0 050 metres SYSTEM Passcode Parameter Details Entered Values No Description Default 1 2 3 4 5 P921 Enable Code 1 Yes P922 Passcode 1997 Backup Parameter Details Entered Values No Description Default 1 2 3 4 5 P925 Parameter Backup 0 No System Information Parameter Details Entered Values No Description De...

Страница 206: ... 1 2 3 4 5 P935 Off Colour 3 Yellow P936 Alarm Colour 1 Red P937 Pump Colour 2 Green P938 Control Colour 2 Green P939 Miscellaneous Colour 2 Green Daylight Save Parameter Details Entered Values No Description Default 1 2 3 4 5 P970 DST Enable 0 P971 DST Differen 01 00 02 00 P972 DST Start Time 02 00 P973 Start Day 8 P974 Start Week 1 P975 Start Month 3 P976 DST End Time 02 00 P977 End Day 8 P978 E...

Страница 207: ...ocol 0 Modbus RTU P132 Device Address 126 P133 Device Baud 19200 P134 Parity 2 Even P135 Stop Bit 1 One Stop P136 Data Format 0 Unsigned Int P137 Delay in ms 5 milli seconds Profibus Parameter Details Entered Values No Description Default 1 2 3 4 5 P132 Device Address 126 P143 Addr Locked 0 No Remote Alarm Parameter Details Entered Values No Description Default 1 2 3 4 5 P144 Call type 0 Off P145 ...