![Pulsar FlowCERT LITE Скачать руководство пользователя страница 95](http://html1.mh-extra.com/html/pulsar/flowcert-lite/flowcert-lite_instruction-manual_1624670095.webp)
Page
87
The
fourth parameter
, and
fifth parameter
, are set to determine the switch
points, “
ON
” and “
OFF
” for the relay. See
miscellaneous
function table
(
P211, 221, 231, 241, 251
) for further information.
When P211, 221, 231, 241, 251 = 1 (Clock)
P213, P223, P233, P243, P253 - Relay Setpoint 1
Relay Setpoints are entered in Hours & Minutes (HH:MM) to set Time at which
relay will energise.
Default = 00:00 (HH:MM)
P214, P224, P234, P244, P254 - Relay Setpoint 2
Relay Setpoints are entered in Minutes to set Time Period that the relay will
remain ON.
Default = 0.00 mins.
When P211, 221, 231, 241, 251 = 2 (Totaliser)
P213, P223, P233, P243, P253 - Relay Setpoint 1
Relay Setpoints are entered as a factor by which the on board totaliser (P820)
should be multiplied by to provide a relay closure.
Default = 0.00
P214), P224, P234, P244, P254 - Relay Setpoint 2
Relay Setpoints are entered in
seconds
to set the
time period
that the relay will
remain
‘
ON’.
Default = 0.00 secs.
Содержание FlowCERT LITE
Страница 1: ...FlowCERT LITE UL INSTRUCTION MANUAL...
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 14: ...Page 6 EC DECLARATION OF CONFORMITY...
Страница 18: ...Page 10 The full dimensions of the enclosure are as shown below...
Страница 37: ...Page 29 This page left blank intentionally...
Страница 77: ...Page 69...
Страница 135: ...Page 127 This page left blank intentionally...
Страница 137: ...Page 129 This page left blank intentionally...