![Pulsar FlowCERT LITE Скачать руководство пользователя страница 115](http://html1.mh-extra.com/html/pulsar/flowcert-lite/flowcert-lite_instruction-manual_1624670115.webp)
Page
107
Limits
P836 mA Low Limit
This parameter sets the lowest value that the mA output will drop to, the
default is 0mA, but you can override this if the device you connect to cannot
for example accept less than 2mA, yet you want to use the 0-20mA range.
Default = 0.00mA
P837 mA High Limit
This parameter sets the highest value that the mA output will rise to, the
default is 20 mA, but you can override this if the device you connect to
cannot for example accept more than 18 mA, yet you want to use the 0-20
mA range.
Default = 20.00mA
Trim
P838 mA Low Trim
If the remote device you are connected to is not calibrated, and not showing
the correct
low value
(reading), then you can trim it using this parameter.
You can either type in the offset directly, or use the arrow keys to move the
output up and down until you get the expected result (reading) on the remote
device that is connected.
P839 mA High Trim
If the remote device you are connected to is not calibrated, and not showing
the correct
high value
(reading), then you can trim it using this parameter.
You can either type in the offset directly, or use the arrow keys to move the
output up and down until you get the expected result (reading) on the remote
device that is connected.
Failsafe
P840 mA Fail-safe Mode
This parameter determines what happens to the mA output in the event of
the unit going into fail-safe mode. The
default
is to do the same as the
system fail-safe
(
P808
), but this can be overridden to force the mA output
to an independent fail-safe mode as follows:
Option
Description
0 = Default
mA output will fail as per
P808
.
1 = Hold
mA output will retain its last known value.
2 = Low
mA output will fail to its
low
condition.
3 = High
mA output will fail to its
high
condition.
Содержание FlowCERT LITE
Страница 1: ...FlowCERT LITE UL INSTRUCTION MANUAL...
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 14: ...Page 6 EC DECLARATION OF CONFORMITY...
Страница 18: ...Page 10 The full dimensions of the enclosure are as shown below...
Страница 37: ...Page 29 This page left blank intentionally...
Страница 77: ...Page 69...
Страница 135: ...Page 127 This page left blank intentionally...
Страница 137: ...Page 129 This page left blank intentionally...