Page
109
Temperature
P852 Temperature Source
This parameter determines the source of the temperature measurement. By
default
it is set to External Range “A” (
P852=4
), which will use an external
temperature sensor with range -25˚C to 50˚C. If for any reason, no
temperature input is received, then the
Fixed Temp
value is used, as set by
P854
.
The temperature source can be specifically set as follows:
Option
Description
1 = Automatic
Will automatically select transducer
temperature sensor, if available, or fixed
temperature (P854) if no temperature
sensor found.
2 = Xducer
Always uses temperature reading from
transducer.
3 = Fixed
Always uses fixed temperature (P854)
4 = Ext Range “A”
(Default)
Uses an optional external temperature
sensor with an operating range of -25
o
C to
50
o
C.
5 = Ext Range “B”
Uses an optional external temperature
sensor with an operating range of -25
o
C to
125
o
C.
P854 Fixed Temperature
This parameter sets the temperature, in degrees centigrade to be used if
P852
(
Temperature Source
) =
3
. Default = 20
o
C
Содержание FlowCERT LITE
Страница 1: ...FlowCERT LITE UL INSTRUCTION MANUAL...
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 14: ...Page 6 EC DECLARATION OF CONFORMITY...
Страница 18: ...Page 10 The full dimensions of the enclosure are as shown below...
Страница 37: ...Page 29 This page left blank intentionally...
Страница 77: ...Page 69...
Страница 135: ...Page 127 This page left blank intentionally...
Страница 137: ...Page 129 This page left blank intentionally...