P128 TrackThrAdd
This is only activated when noise floor is raised, such that the noise floor is
more than P111 away from the normal floor without flow. This causes the
flow to be tracked at a lower flow index so that compensation can be
applied.
Min = 20, Max = 2000
Default = 400
P134 Particle Density
This parameter is used to set the type of material being measured in the pipe
that the FlowPulse is attached to.
Option
Description
0 = Very Low
Material has very low particle density
1 = Low
Material has low particle density
2 = Medium (Default)
Material has medium particle density
3 = High
Material has high particle density
4 = Very High
Material has very high particle density