Page 35
Alarm ID
Description
Setpoints
1=General (Default)
Relay goes “ON” when
the value reaches the ON
setpoint and goes “OFF”
when the value reaches
the OFF setpoint.
P2
1
3, 2
2
3 is ON
Setpoint;
P2
1
4, 2
2
4 is OFF
Setpoint
2= High
Relay goes “ON” when
the value rises to the ON
setpoint and goes “OFF”
when the value lowers to
the OFF setpoint.
ON> OFF
Relay Setpoints
P2
1
3, 2
2
3 and
P2
1
4, 2
2
4
Setpoints, can be
set in any order as
the unit ‘knows’
that you are setting
a high level alarm.
3= Hi-Hi
Same as 2 = High, but
different identifier.
4= Low
Relay goes “ON” when
the value lowers to the
ON setpoint and goes
“OFF” when the value
rises to the OFF setpoint.
ON<OFF Relay
Setpoints
P2
1
3, 2
2
3 and
P2
1
4, 2
2
4.
Setpoints, can be
set in any order as
the unit ‘knows’
that you are setting
a low level alarm.
5= LoLo
Same as 4=Lo, but
different identifier.
6= In bounds
Relay goes “ON” if
value is inside the zone
between the two
setpoints.
Relay Setpoints,
P2
1
3, 2
2
3 and
P2
1
4, 2
2
4 can be
set in any order as
the unit ‘knows’
that you are setting
an inbounds alarm.
7= Out of bounds
Relay goes “ON” if
value is outside the zone
between the two
setpoints.
Relay Setpoints
P21
3
, 2
2
3 and
P2
1
4, 2
2
4 can be
set in any order as
the unit ‘knows’
that you are setting
an out of bounds
alarm.
Содержание Flow Monitor
Страница 1: ...Flow Monitor INSTRUCTION MANUAL...
Страница 2: ......
Страница 4: ......
Страница 10: ...Page 4 EU Declaration of Conformity...
Страница 17: ...Page 11 Your Flow Monitor can be programmed directly via the integral keypad...
Страница 26: ...Page 20 This page left blank intentionally...
Страница 61: ...Page 55...