P983 Test Max
This parameter determines the maximum of the simulated measurement
values.
Default = 1000
P984 Test Min
This parameter determines the minimum of the simulated measurement
values
Default = 0
Hardware
P991 Hard Test
When this parameter is selected, the unit will test the following in turn:
•
LED’s
. Watch them change colour as shown on the display and
press
ENTER
if they operate as shown.
•
Relays
. Press a numeric key, corresponding to the number of the
relay you wish to test, and the relay will change state each time the
key is pressed. If you press any other key, other than a valid relay
number, then the test will end.
•
Segments
. All the segments on the LCD are lit up so you can see if
they all work. Press
ENTER
to end the test.
•
Keys
. You should press each key to confirm it works, with a
counter showing how many more keys remain un-pressed. Be sure
to press the
CANCEL
key last as this will show if all keys were
pressed or not. If they were not, then an error message is displayed.
P992 Output Test
This parameter will allow you to force a specified current on to the output to
test any equipment that it is connected to. The figure you enter will be
generated by the output.
P993 Relay Test
Press a numeric key corresponding to the number of the relay you wish to
test, and the relay will change state each time the key is pressed. If you press
any other key, other than a valid relay number, then the test will end.
Содержание Flow Monitor
Страница 1: ...Flow Monitor INSTRUCTION MANUAL...
Страница 2: ......
Страница 4: ......
Страница 10: ...Page 4 EU Declaration of Conformity...
Страница 17: ...Page 11 Your Flow Monitor can be programmed directly via the integral keypad...
Страница 26: ...Page 20 This page left blank intentionally...
Страница 61: ...Page 55...