TTFM 6.1 INSTRUCTION MANUAL
22
COMMUNICATION (Optional)
Press
or
to position curser at Communication, and
to enter. Use
or
to position cursor before each menu item and
to enter. When settings are
completed press
to store and
again to return to the Main Menu.
MODBUS Protocol Information:
Transceiver:
2-wire, half-duplex
Data format:
8 Data Bits
Floating Point Byte
Order:
ABCD
Termination:
Jumper JP1 selectable 120Ω resistor. TB1 & TB2 =
OFF, TB2 & TB3 = ON
Biasing:
None
HART® (Highway Addressable Remote Transducer) Protocol Information:
HART Version:
7.0
Device
Description
Files:
DD files allow the user’s handheld HART
communicator to fully configure the TTFM 6.1 Pulsar
Measurement provides DD files for the Emerson 475
Communicator. The files are included in the USB
drive provided with your TTFM 6.1 meter. You may
also request the files from Pulsar Measurement by
calling or emailing us at
.
Warning:
The TTFM 6.1 and associated DDs are
pending certification from the Fieldcomm Group.
Connections:
HART Protocol uses a digital signal superimposed on
the 4-20mA output. When the 4-20mA output of the
TTFM 6.1 is connected with a load resistor (230Ω to
600Ω), the HART communicator can be connected
on the loop in order to communicate.