Verify Data Exchange
5604-RIO-PDPMV1
♦
ProLinx Standalone
Rockwell Automation® Remote I/O to PROFIBUS DP-V1 Master Gateway
ProSoft Technology, Inc.
Page 33 of 45
November 20, 2008
3
In the following illustration, the ProSoft Configuration Builder diagnostics
window shows the result of the command in the 5604-RIO-PDPMV1
database.
4
The hexadecimal data includes the following values:
o
A hex value of 3 represents a PROFIBUS Master.
o
A hex value of 4 represents a PROFIBUS Slave.
o
A hex value of 0 represents a PROFIBUS Slave that is offline.
In the illustration above, register 0304 (the bytes are swapped) indicates that
Slave address 0 is offline. The Master is at address 1. The second register
(0004) indicates that Slave address 2 is offline and Slave address 3 is online.
The third register (0000) indicates that slaves 4 and 5 are online.