The minimum and default values are defined by the PLX51-PBM Default
Watchdog setting in the PLX51-PBM PROFIBUS configuration.
Group Membership
Specifies which groups the slave belongs to. A slave can be in multiple
groups at a time (from 1 through 8). Groups are used by the master
when it sends a Sync or Freeze command. PROFIBUS Group
checkboxes are enabled when Sync Mode or Freeze Mode checkboxes
are checked.
Freeze Enabled
User data transmission Synchronization control commands enable the
synchronization of inputs. Freeze Mode field is unchecked by default.
Sync Enabled
User data transmission Synchronization control commands enable the
synchronization of outputs. Sync Mode is unchecked by default.
Byte/Word Swap Option
This parameter will reformat the input and output Profibus DPV0
communication data. Below are the reformat options if the normal data
format is AA BB CC DD:
None
BB AA
DD CC BB AA
CC DD AA BB
Force Data to Zero on
Communication Failure
When this parameter is set it will force the last data received from a DP
device to be forced to zero if the DPV0 communication to that specific
device is lost.