PLX51-PBM
Operation
PROFIBUS DPV0/DPV1 Master or Slave to EtherNet/IP™ or Modbus® Gateway
User Manual
ProSoft Technology, Inc.
Page 123 of 196
DisabledByOutputAssembly
This bit indicates if the device has not been enabled for data
exchange in the PLX51-PBM device enable control bits.
1
– Device has
not
been enabled for data exchange
0
– Device has been enabled for data exchange
DeviceError
This bit indicates an error with the device.
1
– Device has an error.
0
– Device has no error.
The error flag will be set when one of the following conditions
occur:
If there is an ident mismatch during slave parameterization,
When receiving any form of FDL fault (data link layer fault). For
example: SAP Not Activated or Resource Not Available.
When the data size of the DPV0 data exchange does not match
what has been configured in the PLX50CU.
This Error flag is transient and will clear once a valid response
is received.
AlarmPending
Indicates the device has an alarm pending on the local
PROFIBUS
network. When the specific bit is set ‘1’ then the
device has an alarm pending that must be unloaded and when
the bit is off ‘0’ the device does not have an alarm pending.
0
– The node has no alarm pending
1
– The node has an alarm pending
DiagnosticsPending
Indicates the device has diagnostics pending on the local
PROFIBUS
network. When the specific bit is set ‘1’ then the
device has diagnostics pending that must be unloaded and
when the bit is off ‘0’ the device does not have any diagnostics
pending.
0
– The node has no diagnostics pending
1
– The node has diagnostics pending
OutputAssemblyNodeAddrMismatch
This bit indicates that there is a mismatch between the actual
device station address and the expected Logix mapping station
address.
0
– Station address matches
1
– Station address mismatch
MappingCRCMismatch
If there is a mismatch in the mapping between Logix and the
PLX51-PBM it can result in data appearing in the incorrect
location which means the user can be sending incorrect data to
a device which can have unpredicted results.
0
– The mapping for the output data is correct.
1
– There is a mapping mismatch in the output data.
SlaveClearOpMode
When the PLX51-PBM is in
Slave Mode
; this will indicate that
the respective slave is in fieldbus CLEAR mode (received from
the DP Master on the network).
0
– Slave Station is in CLEAR fieldbus mode.
1
– Slave Station is
not
in CLEAR fieldbus mode.
SlaveAlarmAck
When the PLX51-PBM is in
Slave Mode
; this will indicate that
the respective emulated slave has received an
acknowledgement for the pending alarm.
0
– Slave Station has received an Alarm Acknowledgement for
last pending alarm.
1
– No Alarm Acknowledgement have been received for a
pending alarm or there is no alarm pending.
StationNumber
The station number of the specific slave device.
DeviceMappingCRC
The checksum of the Mapping for the specific slave device.
DeviceSpecificInputDataFields
The tags created for the input data will be slave specific.