PLX51-PBM
Operation
PROFIBUS DPV0/DPV1 Master or Slave to EtherNet/IP™ or Modbus® Gateway
User Manual
ProSoft Technology, Inc.
Page 104 of 196
DeviceDataExchangeActive
Indicates the nodes that are online and exchanging DPV0 data on
the local PROFIBUS network. Each bit represents a node. When the
specific bit is set ‘1’ then the device is online and exchanging data
and when th
e bit is off ‘0’ the device is not exchanging data on the
PROFIBUS network.
Bit 0
– Node 0 Exchanging DPV0 Data
Bit 1
– Node 1 Exchanging DPV0 Data
Bit 126
– Node 126 Exchanging DPV0 Data
DeviceAlarmPendingFlags
Indicates the nodes that have an alarm pending on the local
PROFIBUS network. Each bit represents a node. When the specific
bit is set ‘1’ then the device has an alarm pending that must be
unloaded and when the bit is off ‘0’ the device does not have an
alarm pending.
Bit 0
– Node 0 has an alarm pending
Bit 1
– Node 1 has an alarm pending
Bit 126
– Node 126 has an alarm pending
DeviceDiagnosticPendingFlags
Indicates the nodes that have diagnostics pending on the local
PROFIBUS network. Each bit represents a node. When the specific
bit is set ‘1’ then the device has diagnostics pending that must be
unloaded and when the bit is off ‘0’ the device does not have any
diagnostics pending.
Bit 0
– Node 0 has diagnostics pending
Bit 1
– Node 1 has diagnostics pending
Bit 126
– Node 126 has diagnostics pending