PLX51-PBM
Setup
PROFIBUS DPV0/DPV1 Master or Slave to EtherNet/IP™ or Modbus® Gateway
User Manual
ProSoft Technology, Inc.
Page 33 of 196
3.5.5
PROFIBUS – Slave Mode
The PROFIBUS configuration (in Slave Mode) is shown in the figure below. The
PLX51-PBM PROFIBUS configuration window is opened by either double clicking on
the module in the tree or right-clicking the module and selecting
Configuration
.
Figure 3.24
– PLX51-PBM PROFIBUS configuration – Slave Mode
The PROFIBUS configuration consists of the following parameters:
Table 3.5 - PROFIBUS configuration parameters
– Slave Mode
Parameter
Description
BAUD Rate
Baud Rate (in Kbps) of the PROFIBUS network: 9.6, 19.2, 45.45,
93.75, 187.5, 500, 1500, 3000, 6000 or 12000 Kbps. The baud rate selected
should be supported by all slaves in the configuration. The baud rate should be
selected depending on the cable length, see chapter “PROFIBUS DP”
DP Slaves Online
during Communication
Failure
This parameter will allow the DP DPV0 communication to continue when
communication it lost on either Modbus (Master or Slave) or EtherNet/IP
Explicit Messaging. When this is not set, the DP DPV0 communication will be
stopped when the communication to the previously mentioned interfaces is
lost.