MVI46-PDPMV1 ♦ SLC Platform
Configuring the MVI46-PDPMV1 Module
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 27 of 160
March 25, 2011
For the sample application, the
Input Data Size
and
Output Data Size
values
should both be
768
.
4
Click
OK
to save your settings and return to the
ProSoft Configuration Builder
window.
At this time, you may wish to rename the
Default Project
and
Default Location
folders in the tree view.
To rename an object
1
Select the object, and then click the right mouse button to open a shortcut
menu. From the shortcut menu, choose
R
ENAME
.
2
Type the name to assign to the object.
3
Click away from the object to save the new name.
2.2.1 Input Data Size
0
to
768
Number of words to transfer from the PROFIBUS input image to the controller.
2.2.2 Output Data Size
0
to
768
Number of words to transfer to the PROFIBUS output image from the controller.