MVI46-PDPMV1 ♦ SLC Platform
Diagnostics and Troubleshooting
PROFIBUS DPV1 Master
User Manual
ProSoft Technology, Inc.
Page 107 of 160
March 25, 2011
Viewing PROFIBUS Data
Press
[2]
to view PROFIBUS data. Use this command to view information related
to the status of each slave in the PROFIBUS network, and to verify that each
slave is configured (SLAVE CFG LIST), exchanging data with the Master
(TRANSFER LIST) and in diagnostic mode (SLAVE DIAG LIST).
You can also check the module's operation state, where:
00 = Offline
40 = Stop
80 = Clear
C0 = Operate
Viewing Control Registers
Press
[3]
to view information about the PROFIBUS Master’s Control Registers.
Use this command to view general information about the module, such as the
firmware version and its serial number. The module status contains two possible
codes:
0400 = module is running but not communicating with slaves
0401 = module is running and communicating with slaves
If the module is in STOP mode, the status code is displayed as 0400.
Exiting the Program
Press
[ESC]
to restart the module and force all drivers to be loaded. The module
will use the configuration stored in the module's flash memory to configure the
module.