Configuring the MVI46-PDPMV1 Module
MVI46-PDPMV1 ♦ SLC Platform
User Manual
PROFIBUS DPV1 Master
Page 50 of 160
ProSoft Technology, Inc.
March 25, 2011
2.4
Verifying Correct Operation
The final step is to verify that the MVI46-PDPMV1 module is communicating with
the PROFIBUS slave. Choose the method that best suits your connection and
proximity to the modules and the processor.
If you are able to view the module directly: Look at the PROFIBUS LEDs on
the MVI46-PDPMV1 (page 50)
If you are able to connect to the module using ProSoft Configuration Builder
and a serial cable: View the online status of the PROFIBUS network (page
51)
If you are able to connect to the module using ProSoft Configuration Builder
and a serial cable: View the Fieldbus Data from the MVI46-PDPMV1’s
Configuration/Debug menu (page 53)
If you are able to connect to the processor using RSLogix 500: View the Data
Files in RSLogix 500 (page 56)
If you are able to connect to the processor using RSLogix 500: Send a
Mailbox Message in RSLogix 500 (page 58)
2.4.1 Checking the PROFIBUS LEDs on the MVI46-PDPMV1
If all four PROFIBUS LEDs (page 99) are illuminated green, then the
PROFIBUS Master is communicating and exchanging data with all configured
PROFIBUS slaves.
If the COM STAT LED is green and flashing, the PROFIBUS Master is
communicating and exchanging data with at least one of the configured
slaves.
If the COM STAT LED is red, there is a communication or configuration error.
If the COM STAT LED is off, the PROFIBUS Master is not communicating
with any slaves. The most likely reason is that the slaves are not correctly
configured.
After restarting the MVI46-PDPMV1 Master and the PROFIBUS slave, look at
the PROFIBUS cable connection. If all the PROFIBUS LEDs on the MVI46-
PDPMV1 are illuminated green, then the Master is communicating
successfully with all slaves.