Ladder Logic
MVI56E-MNETR ♦ ControlLogix Platform
User Manual
Modbus TCP/IP Interface Module with Reduced Data Block
Page 88 of 175
ProSoft Technology, Inc.
June 14, 2011
MNETRINITOUTDATA
Used to bring the Module into a known state after a restart operation.
Name
Data Type
Description
TriggerInitOut
BOOL
Trigger Output Data Initialization.
InitializeOutputData
INT
Quantity of Blocks(200 words of "ReadData")
for the module to read from the PLC. [0 to 24]
means a qty of 1 to 25
RetInitOutData
INT[200]
Returned Initialization output data
TriggerInitOutPending
BOOL
Set after the ladder has sent an event cmd to
the module and is waiting for the status to be
returned
RetInitOutDataBlkID
INT
Returned Block ID for Returned Initialize
Output Data command.
InitOutBlkIDLim
INT
Block Index Limit for ReadData size of the
array