Configuring the MVI56E-MNETR Module
MVI56E-MNETR ♦ ControlLogix Platform
User Manual
Modbus TCP/IP Interface Module with Reduced Data Block
Page 56 of 175
ProSoft Technology, Inc.
June 14, 2011
Pass-Through Mode
0
,
1
,
2
or
3
This parameter specifies the pass-through mode for write messages received by
the MNET and MBAP server ports.
If the parameter is set to
0
, all write messages will be placed in the module’s
virtual database.
If a value of
1
is entered, write messages received will be sent to the
processor as unformatted messages.
If a value of
2
is entered, write messages received will be sent to the
processor as formatted messages.
If a value of
3
is entered, write messages received will be sent to the
processor with the bytes swapped in a formatted message.
Duplex/Speed Code
0
,
1
,
2
,
3
or
4
This parameter allows you to cause the module to use a specific duplex and
speed setting.
Value =
1
: Half duplex, 10 MB speed
Value =
2
: Full duplex, 10 MB speed
Value =
3
: Half duplex, 100 MB speed
Value =
4
: Full duplex, 100 MB speed
Value =
0
: Auto-negotiate
Auto-negotiate is the default value for backward compatibility. This feature is not
implemented in older software revisions.
2.1.4 MNET Client x
This section defines general configuration for the MNET Client (Master).
Error/Status Pointer
-1
to
4990
Starting register location in virtual database for the error/status table for this
Client. If a value of
-1
is entered, the error/status data will not be placed in the
database. All other valid values determine the starting location of the data.
Command Error Pointer
-1
to
4999
This parameter sets the address in the internal database where the Command
Error List data will be placed so that it may be moved to the processor and
placed into the
ReadData
array. Therefore, the value entered should be a
module memory address in the Read Data area. If the value is set to
-1
, the
Command Error List data will not be stored in the module's internal database and
will not be transferred to the processor's
ReadData
array.