MVI56E-MNETR ♦ ControlLogix Platform
Configuring the MVI56E-MNETR Module
Modbus TCP/IP Interface Module with Reduced Data Block
User Manual
ProSoft Technology, Inc.
Page 61 of 175
June 14, 2011
Enable
N
O
(0),
Y
ES
(1), or
C
ONDITIONAL
(2)
This field defines whether the command is to be executed and under what
conditions.
Value
Description
N
O
(0)
The command is disabled and will not be executed in the normal polling
sequence.
Y
ES
(1)
The command is executed each scan of the command list if the
Poll Interval
time
is set to zero. If the
Poll Interval
time is set to a nonzero value, the
command will be executed when the interval timer expires.
C
ONDITIONAL
(2) The command will execute only if the internal data associated with the
command changes. This value is valid only for write commands.
Internal Address
0
to
4999
(for word-level addressing)
or
0
to
65535
(for bit-level addressing)
This field specifies the database address in the module's internal database to use
as the destination for data brought in by a read command or as the source for
data to be sent out by a write command. The database address is interpreted as
a bit address or a 16-bit word (register) address, depending on the Modbus
Function Code used in the command.
For Modbus functions 1, 2, 5, and 15, this parameter is interpreted as a bit-
level address.
For Modbus functions 3, 4, 6, and 16, this parameter is interpreted as a word-
or register-level address.
Poll Interval
0
to
65535
This parameter specifies the minimum interval to execute continuous commands
(
Enable
code of
1
). The parameter is entered in tenths of a second. Therefore, if
a value of
100
is entered for a command, the command executes no more
frequently than every 10 seconds.