MVI56E-MNETR ♦ ControlLogix Platform
Configuring the MVI56E-MNETR Module
Modbus TCP/IP Interface Module with Reduced Data Block
User Manual
ProSoft Technology, Inc.
Page 71 of 175
June 14, 2011
2.3
Using CIPconnect
®
to Connect to the Module
You can use CIPconnect
®
to connect a PC to the ProSoft Technology MVI56E-
MNETR module over Ethernet using Rockwell Automation’s 1756-ENBT
EtherNet/IP
®
module. This allows you to configure the MVI56E-MNETR network
settings and view module diagnostics from a PC. RSLinx is not required when
you use CIPconnect. All you need are:
The IP addresses and slot numbers of any 1756-ENBT modules in the path
The slot number of the MVI56E-MNETR in the destination ControlLogix
chassis (the last ENBTx and chassis in the path).
To use CIPconnect, follow these steps.
1
In the
Select Port
dropdown list, choose
1756-ENBT
. The default path
appears in the text box, as shown in the following illustration.
2
Click
CIP
P
ATH
E
DIT
to open the
CIPconnect Path Editor
dialog box.