
Reference
MVI56E-MNETR ♦ ControlLogix Platform
User Manual
Modbus TCP/IP Interface Module with Reduced Data Block
Page 162 of 175
ProSoft Technology, Inc.
June 14, 2011
5.8.4 Downloading the Sample Program to the Processor
To download the sample program from RSLogix 5000 to the ControlLogix
processor
Note
: The key switch on the front of the ControlLogix module must be in the REM
position.
1
If you are not already online to the processor, open the
C
OMMUNICATIONS
menu, and then choose
D
OWNLOAD
.
RSLogix will establish communication
with the processor.
2
When communication is established, RSLogix will open a confirmation dialog
box. Click the
D
OWNLOAD
button to transfer the sample program to the
processor.
3
RSLogix will compile the program and transfer it to the processor. This
process may take a few minutes.
4
When the download is complete, RSLogix will open another confirmation
dialog box. Click
OK
to switch the processor from PROGRAM mode to RUN
mode.
Note:
If you receive an error message during these steps, refer to your RSLogix documentation to
interpret and correct the error.