
Reference
MVI56E-MNETR ♦ ControlLogix Platform
User Manual
Modbus TCP/IP Interface Module with Reduced Data Block
Page 156 of 175
ProSoft Technology, Inc.
June 14, 2011
Select the
1756-M
ODULE
(Generic 1756 Module) from the list and click
OK.
This action opens the
N
EW
M
ODULE
dialog box.
Parameter
Value
Name
Enter a module identification string. The recommended value
is MNETR.
Description
Enter a description for the module. Example: Modbus TCP/IP
Interface Module with Reduced Data Block.
Comm Format
Select
D
ATA
-INT
(Very Important)
Slot
Enter the slot number in the rack where the MVI56E-MNETR
module will be installed.
Input Assembly Instance
1
Input Size
42
Output Assembly Instance
2
Output Size
42
Configuration Assembly
Instance
4
Configuration Size
0
Enter the Name, Description and Slot options for your application. You must
select the
C
OMM
F
ORMAT AS
D
ATA
-
INT
in the dialog box, otherwise the
module will not communicate over the backplane of the ControlLogix rack.
Click OK to continue.