cli> enclosure –m –t <enable>
<enable> = 0
- Disable thermal manager function
<enable> = 1
- Enable thermal manager function
cli> enclosure –m –c <sensor id> <threshold>
<sensor id> = 1~10
- Any one thermal sensor ID between 1 to 10
<threshold> = 68 ~ 72
- Critical thermal threshold; between 68 to 72 degree C, if the sensor is located on IO Module.
<threshold> = 57 ~ 61
- Critical thermal threshold; between 57 to 61 degree C, if the sensor is located outside the IO Module.
cli> enclosure –m –w <sensor id> <threshold>
<sensor id> = 1~10
- Any one thermal sensor ID between 1 to 10
<threshold> = 61 ~ 65
- Warning thermal threshold; between 61 to 65 degree C if the sensor is located on IO Module.
<threshold> = 47 ~ 51
- Warning thermal threshold; between 47 to 51 degree C if the sensor is located outside the IO Module.
cli> enclosure –m –f <min_fan_lvl>
- f <min_fan_lvl>
- Minimum fan speed when system is normal
<value> = 1 ~ 10
J5600/J5800 allow to set 1 ~ 10
J5300/J5320 allow to set 1 ~ 6
50
VTrak J5000 Series
Promise Technology
Содержание VTrak J5000 Series
Страница 28: ...Drive slot numbering on VTrak J5300 Drive slot numbering on VTrak J5320 21 12G SAS JBOD User Guide ...
Страница 36: ...DB 9 pinout for RJ 11 to DB 9 serial cable 29 12G SAS JBOD User Guide ...
Страница 94: ...87 VTrak J5800 Zoning Configuration 3 Four zones divided access 12G SAS JBOD User Guide ...