l
- Output current in mA
f
- Stroke rate in strokes/min
L
- Current litre output
L
max
-
„ Capacity at 20 mA“
f
max
- Maximum stroke rate in strokes/min
The current output emits a current of 20 mA above the value set here for
„Capacity at 20 mA“
and above.
In the
„Contact“
and
„Batch“
operating modes, f is the stroke rate which is
set in the "Stroke rate" continuous display.
8.6.7 Settings for the “Diaphragm break” function (DIAPHRAGM BREAK menu)
Continuous
display
Main menu
Mode
Settings
Service
Information
Language
Settings
Dosing monitor
Relay
Diaphragm break
System
End
Diaphragm break
Error
Warning
Inactive
Using the "Diaphragm break" programmable function, you can match the
behaviour under fault conditions of the pump to your requirements, pro‐
vided an electrical membrane rupture sensor is connected.
There is a choice, of whether a membrane rupture should lead to an
„Error“
or a
„Warning“
. If
„Inactive“
is set, the pump does not react to a
diaphragm rupture, however the symbol dia indicates that an electrical
membrane rupture sensor is connected.
8.6.8 Settings in the "System" menu" (SYSTEM menu)
Analog output
Unit
End
Main menu
Mode
Settings
Service
Information
Language
Settings
Calibrate
Dosing
Diaphragm break
System
End
Unit
Liter
Gallon (U.S.)
Continuous
display
In the
„System“
menu you can select whether the pump uses
„Liter“
or
„Gallon (US)“
as the
„Unit“
.
8.7 Service (SERVICE menu)
The following can be carried out from this menu:
1 -
„Clear counter“
2 - Set contrast (Menu
„Display“
)
3 -
„HMI logout“
4 - Set safety settings for operating menu (
„Safety“
menu)
Setting
59
Содержание Sigma/ 2 Control S2Cb