8.6.6 Settings for the “Analog output” function (ANALOG OUTPUT menu)
Analog output
Range
Function
End
Main menu
Mode
Settings
Service
Information
Language
Settings
Analog
Auxiliary freq.
Calibrate
Dosing
Analog output
Range
0..20mA
4..20mA
Function
Strokes / min
Capacity
Capacity at 20mA
Continuous
display
Using the "Analog output" programmable function, you can match the
pump current output signal (optional) to your requirements.
The signal I of the current output signal one of the three following varia‐
bles:
n
Strokes/min
n
Capacity
n
Capacity at 20 mA
In the "Stop" or "Pause" states (either because of a fault or operation) or
"Pause" the current output transmits a current of 4 mA or 0 mA.
The pump calculates the signal for
„Strokes / min“
according to the fol‐
lowing formula (here for the range 4...20 mA):
I(4...20) = 16 x (f/fmax) + 4
with
l
- Output current in mA
f
- Stroke rate in strokes/min
fmax - Maximum stroke rate in strokes/min
In the
„Contact“
and
„Batch“
operating modes, f is the stroke rate which is
set in the "Stroke rate" continuous display.
The pump calculates the signal for
„Capacity“
according to the following
formula (here for the range 4...20 mA):
I(4...20) = 16 x (f/f
max
) x (H/100) + 4
with
l
- Output current in mA
f
- Stroke rate in strokes/min
H
- Stroke length in %
f
max
- Maximum stroke rate in strokes/min
In the
„Contact“
and
„Batch“
operating modes, f is the stroke rate which is
set in the "Stroke rate" continuous display.
This menu item is only available with a calibrated pump.
The pump calculates the signal for
„Capacity at 20 mA“
according to the
following formula (here for the range 4...20 mA):
I(4...20) = 16 x(L/L
max
) + 4
with
To
„Strokes / min“
To
„Capacity“
To
„Capacity at 20 mA“
Setting
58
Содержание Sigma/ 2 Control S2Cb
Страница 63: ...In the LANGUAGE menu you can select the desired operating lan guage Setting 63...
Страница 99: ...99...