Advanced Settings Page
Professional Series Network Thermostat Configuration Guide, Release 3.0
3-37
Part No. 600-01000-200, Rev. 2
Use
Table 3-6
to configure the
Advanced Settings
for a parameters.
Table 3-6 Advanced Settings Fields - HVAC Fuel Burner Field Descriptions
Field
Description
HVAC System Type
Select the type of HVAC system, either
Fuel Burner
(default)
or
Heat Pump
HVAC systems as follows:
Fuel Burner
(default) – The HVAC system burns fossil
fuels (e.g. gas or oil). Typically the system includes either an
oil or gas fired boiler or furnace. See
Figure 3-15 on
page 3-36
and continue with
If Your HVAC System is a Fuel
Burner (page 3-37)
.
Heat Pump
– Specifies that the HVAC system is based on
an electric compressor. See
Figure 3-14 on page 3-35
and
continue with
If Your HVAC System is a Heat Pump (page
3-38)
.
Note: When selecting between either
Fuel Burner
or
Heat
Pump
or
between Heat Pump
and
Fuel Burner
, the HVAC
Mode must be set to Off prior to selecting the opposite setting.
See the
Status & Control Page (page 3-9)
.
If Your HVAC System is a Fuel Burner
Heat Control
Select the HVAC control for this thermostat. This parameter
describes the thermostat capability to control a single stage or
dual stage heating system. The thermostat can also be disabled
from controlling a heating system and instead operate as a
cool-only thermostat. (See
Cool Control (page 3-38)
.)
Disable
– No heating system exists. (A/C only thermostat.)
1H
– Enables the heating system as a standard single stage
system.
2H
(default) – Enables the heating system as a dual stage
system.
2
nd
Stage Offset
Specify the second stage heat set point temperature referenced to
the first stage heat set point temperature. This parameter is only
enabled when
2H
Heat Control
is selected, otherwise it is
disabled. (e.g. If the first stage temperature set point is set to
70°F, and this parameter were set to -3°F, the second stage heat
would activate at or below 67°F). Temperatures include:
0, -2, -3, -4, -5, -6 °F (0, -1.0, -1.5, -2.0, -2.5, -3.0 °C)
– Second
stage heat temperature offset from first stage heat set point
temperature.