General Settings Page
Professional Series Network Thermostat Configuration Guide, Release 3.0
3-17
Part No. 600-01000-200, Rev. 2
High Humidity Limit
(NT150e/h and NT160e/h only)
Select a value or
Disable
to indicate the high humidity threshold
detection status. This value is monitored by the thermostat and
compared against the current
Relative Humidity
. If the current
Relative Humidity
rises above this value, an alarm condition is
set and the status is displayed on the
Status and Control Page
(page 3-9)
. In addition, this alarm is sent to the Proliphix web
site to trigger an email notification if this function is
Enabled
.
Disable
(default) – No high humidity limit is set.
10%RH to 90%RH
– High Humidity Limit in 5%
increments.
This is a major (red) alarm condition.
If a
High Humidity Limit
alarm is set and is noted in the
High
Humidity Dismiss
field then the
Condition Repaired
box must
be checked and the relative humidity must be below the
High
Humidity Limit
or the
High Humidity Limit
must be set to
Disable
for the alarm condition to be cleared upon a
Submit
.
High Temp(erature) Dismiss
If a
High Temp Limit
alarm is set and is noted in the
High
Temp Dismiss
field then the
Condition Repaired
box must be
checked and the
Zone Temperature
must be below the
High
Temp Limit
or the
High Temp Limit
must be set to
Disable
for
the alarm condition to be cleared upon a
Submit
.
Filter (change) Reminder
Select an interval between
Disable
(default) and
365
days to
remind you that the HVAC system requires maintenance. This
feature allows you to set time intervals between changing and/or
cleaning the HVAC filter. If enabled, an alarm condition is set
after the pre-set interval has expired, and is displayed on the
Status & Control Page (page 3-9)
. In addition, this alarm is sent
to the Proliphix web site to trigger an email notification if this
function is
Enabled
.
This is a minor (yellow) alarm condition.
Disable
(default) – Interval reminder disabled.
10, 30, 60, 90, 120, 240, 365 Runtime Days
– The runtime
interval after which an alarm will be set to remind the user of
the need for HVAC maintenance.
The TMI displays the following additional fields upon different settings and conditions of the
Filter
Reminder
state.
Filter Usage
The TMI displays this field when
Filter Reminder
in enabled.
x.x Runtime Days
– Displays a running tally of
Runtime Days
(x.x) which have elapsed since the previous
Filter Last
Replaced
date. If this value is greater than the preset
Runtime
Days
, it is displayed in
red
and an alarm is generated indicating
that the
Filter Reminder
interval has expired.