Professional Series Network Thermostat Configuration Guide, Release 3.0
Part No. 600-01000-200, Rev. 2
CHAPTER 3: Configuring the Thermostat Using the TMI
Port
Enter the Syslog server IP port, which allows you to use a
custom program to receive alarm/alert notifications.
wxyz
– Four digit (max) standard IP port number designation.
The default port number is
514
.
Repeat Interval
Select the Syslog messaging periodic interval. This is the rate at
which Syslog messages are emitted from the thermostat.
1, 5, 30, 60
–The amount of time in minutes between successive
Syslog messages sent by the thermostat after an error event and
before the error event is cleared.
Syslog alarm/alert messages are sent to the Syslog server every
minute until the alarm/alert condition is cleared on the
thermostat. Alarm/alert messages are sent with a
Local7 Facility
Code
and with a severity level of
Alert
as defined in RFC 3164.
In addition to alarms and alerts, the System Start event
(generated during thermostat start up) is also reported to the
Syslog server. These events are not repetitive but only occur
once when the event occurs.
Table 3-5 Network Settings Field Descriptions (Continued)