Professional Series Network Thermostat Configuration Guide, Release 3.0
Part No. 600-01000-200, Rev. 2
CHAPTER 3: Configuring the Thermostat Using the TMI
Set Point Override
This feature, when used with
Button Lockout
restricts the use of
the thermostat buttons to allow only limited temperature
adjustments to be made above and below the preset temperature
schedules. This field is disabled if
Button Lockout
is set to
Disable
.
0
(default) – No temperature adjustments are allowed. All
thermostat buttons are disabled.
1 through 20
– (Fahrenheit) Allowed temperature limits
above and below the current scheduled temperature settings.
(e.g. If this value is set to 2, the Up and Down buttons may
be used to select a temperature within the range of 2°F
below/above the current scheduled temperature set point.)
.5 through 10
– (Celsius) Allowed temperature limits above
and below the current scheduled temperature settings.
Alarms
Low Temp(erature) Limit
Select a value
or
Disable
to indicate the low temperature
threshold detection status. The value set by this parameter is
monitored by the thermostat and compared against the current
Zone Temperature
. If the current
Zone Temperature
falls below
this value, an alarm condition is set and the status is displayed on
the
Status & Control Page (page 3-9)
. In addition, this alarm will
be sent to the Proliphix web site to trigger an email notification if
this function is
Enabled
.
Disable
(default) – No low temperature limit is set.
-30
°
F(-34.5
°
C) to 200
°
F(93
°
C)
This is a major (red) alarm condition.
Low Temp(erature) Dismiss
If a
Low Temp Limit
alarm is set and is noted in the
Low Temp
Dismiss
field then the
Condition Repaired
box must be
checked and the
Zone Temperature
must be above the
Low
Temp Limit
or the
Low Temp Limit
must be set to
Disable
for
the alarm condition to be cleared upon a
Submit
.
High Temp(erature) Limit
Select a value or
Disable
to indicate the high temperature
threshold detection status. The value set by this parameter is
monitored by the thermostat and compared against the current
Zone Temperature
. If the current
Zone Temperature
rises above
this value, an alarm condition is set and the status is displayed on
the
Status & Control Page (page 3-9)
. In addition, this alarm is
sent to the Proliphix web site to trigger an email notification if
this function is
Enabled
.
Disable
(default) – No high temperature limit is set.
-30
°
F(-34.5
°
C) to 200
°
F(93
°
C)
This is a major (red) alarm condition.
Table 3-2 General Settings Field Descriptions (Continued)
Field
Description