8. ADDITIONAL INFORMATION FOR 

VOLUME 

 
When configuring the unit to irrigate and fertilize in 

volume units, m

3

 and liters respectively, the following 

changes in the “functions” of the controller take place: 

 
 

8.1. PARAMETERS 

 

In the irrigation programming by time, the pre-

irrigation is calculated automatically from the entered 
irrigation value, as the irrigation and the fertilizer are 
applied on the same base, which is the minute. 

 

By volume, the pre-irrigation and post-irrigation val-

ues have to be entered in “m

3

”. 

 

It will start to fertilize once the irrigation has finished 

the pre-irrigation plus the pre-mixing time, if there is one, 
and it will may sure that the fertilizer application does not 
overlap with the post-irrigation volume, in this case, the 
unit would stop fertilizing and the anomaly would be 
recorded. 

 

The volume units in fertilizer parameters are: 
- Pre-irrigation 

0 to 999 m

3

 

- Post-irrigation 

0 to 99 m

3

 

- Separation between fertilizers 

0 to 99 m

3

 

 
The volume units in filter cleaning parameters are: 
- Irrigation volume between cleaning cycles: 

0 to 9999 m

3

.

 

 

In various parameters, the irrigation and the fertili-

zation are configured plus the value of the counters (as 
already explained in section 6.1.). 

 
 

8.2. PROGRAMS 

 

The differences in an irrigation program by volume 

are: 

-Irrigation units 

0 to 999 m

3

 

-Fertilizer units 

0 to 999 liters 

 

P02  04   SMTWTFS   08:15 

I084       F

1

 014         F

2

 009 

 

The modality of parallel fertilization can not be 

done in volume units. 

 
 

8.3. TOTALS 

 

In the totals, the information will be shown in m

3

 

units for the irrigation and in liters for the fertilizers. 

 

8.4. CONSULTATION 

 

For every sector being irrigated, it will display the 

quantity of cubic meters left to irrigate and the liters of 
fertilizer which are still to be applied. 

 

S02   P14    F

1

026     F

2

 000 

I=083        F

3

 007  F

4

 012 

 
 

8.5. ANOMALIES 

 

If no pulses are received from the irrigation water 

counter for more than ten minutes, while any program is 
working, the program will be stopped and the following 
anomaly will appear. 

 

* I. counter malfunction * 

Mon. 11:28 

 

If the controller is fertilizing and no pulses are re-

ceived from the volumetric fertilizer counter, for more 
than ten minutes, the fertilization program being carried 
out would be stopped and the following anomaly would 
be recorded. 

 

* F. counter malfunction * 

Sun. 07:33 

 

Содержание Agronic 2000 Series

Страница 1: ...Manual 19 7 3 Totals 19 7 4 Consultation 20 8 ADDITIONAL INFORMATION FOR VOLUME 22 8 1 Parameters 22 8 2 Programs 22 8 3 Totals 22 8 4 Consultation 22 8 5 Anomalies 22 9 ADDITIONAL INFORMATION FOR DIE...

Страница 2: ...ttempts pre heating automatic stop malfunction detection etc CLEANING OF FILTERS This can be configured from 0 to 9 filters with variable washing time Pause time between filters The washing sequence c...

Страница 3: ...e identifica tion labels correspond with the desired model To decide on the necessary model number of outlets the irrigation sectors needed the number of fertilizers mixers fertilizer pump and filters...

Страница 4: ...n housing In the model with 26 outlets a second additional box is pro vided To maintain the isolation of the unit it is essential to keep the panels closed as well as to install cable glands at the ca...

Страница 5: ...ne working that this one works without the battery as the alternator would increase the equipment power tension mo mentarily To replace the fuse half turn the fuse cover and insert another of the same...

Страница 6: ...more intensity insert external re lays The outlet fuse protects from overloads and short circuits To change it just half turn the cover of the fuse holder take it out and replace it with a similar one...

Страница 7: ...Electro pump 24V Rest Sectors and general outlets 24 V 1 26 26 Start 25 Stop Pre heating Electro pump Rest Sectors and general outlets 26 Start 12 V 25 Stop 12 V Pre heating 12V Electro pump 24V Rest...

Страница 8: ...of 20 to 30 amps Its outlet has to be connected to the terminal cable 50 of the key If the engine stops by electromagnet a supple mentary relay will be installed between the former one and the stop o...

Страница 9: ...l be con nected to the controller to the outlet corresponding to its sector or to the M general valve outlet 4 4 3 Two pump option In this option the second pump or general valve 2 will be connected t...

Страница 10: ...ion for the Fulfillment of the Product Security The fulfillment of the following specifications was demonstrated as indicated in the Official Diary of the European Communities Emissions EN 50081 1 94...

Страница 11: ...utes Stop of sectors when cleaning filters yes or no VARIOUS By volume yes or no Irrigation pulse value 0 to 10000 liters Fertilizer pulse value 0 to 1000 cl Assignation of functions to the inputs Del...

Страница 12: ...9 Number of filters 3 If the previous screen shows that there are filters the following question corresponds to the working time for everyone of them 3 to 999 seconds and the pause between them from 0...

Страница 13: ...has changed minute The input will not start again until the pro gram or its sequences of programs have finished IC FC SC TM GM CS PS 1 2 0 5 0 3 4 The following screens correspond to the detec tion de...

Страница 14: ...s chosen then if the cut in the supply is less than 24 hours when it returns the unit will take up the program at the corresponding chronological point If the shortcut is for more than 24 hours when i...

Страница 15: ...ations of the unit in the fol lowing screen St Start outlet Sp Stop outlet Pr Pre heating outlet Ep Electro pump outlet St Sp Pr Ep 18 17 16 15 In the diesel version it asks for the start and stop tim...

Страница 16: ...hen the program has been chosen and the ENTER key pressed we are now inside and the screen will ask for the remaining details placing the cursor _ on every one of the values After introducing the firs...

Страница 17: ...efined that the fer tilizers will be injected like this The programming will be the same as in series The fertilization in parallel can be done through a multihead injector or with one injector for ea...

Страница 18: ...different irrigations activations in one sector or in a group of sectors only the program 1 have the variable of activation number and frequency between them The frequency time between activations ma...

Страница 19: ...option has to be used very carefully due to the fact that when an outlet is activated in this way the control of malfunctions anomalies totals etc is not carried out To cancel them enter the outlet nu...

Страница 20: ...F2 0 19 I 01 58 F3 0 21 F4 0 15 For every two activated sec tors a screen with their valves will be displayed In the first line shows the sector n program n with the values of the F1 F2 units left an...

Страница 21: ...the unit does not allow any activation of the irrigation programs If the general malfunction input was activated all the outlets will be deactivated and the screen will show this message with the day...

Страница 22: ...ing cycles 0 to 9999 m3 In various parameters the irrigation and the fertili zation are configured plus the value of the counters as already explained in section 6 1 8 2 PROGRAMS The differences in an...

Страница 23: ...carried out prior to starter 9 1 CONSULTATION In the first screen of consult the letters OP will be shown at the end of the first line to indicate that the engine is working and there is oil pressure...

Страница 24: ...24 NOTES R 1189 3...

Отзывы: