Published: 25.03.2022
8 (15)
ML-SER tool display shows how much the current value is tuned. The measured value is shown in
brackets after the tuning value.
1.4.2.3 Output menu
You can change the output scaling of all outputs and the controller output direction through the output
menu. Also, the fixed controller output value and duration can be selected through the menu.
M
OK
OK
Modbus ID
0-10V
Y1-Y4 range
OK
Direct
Output mode
OK
OFF
Fixed output
OK
100%
Fixed output
+/-
OK
12h
Deactivation
OUTPUT
Parameter
Available values
Description
Y1-Y4 range
0-10V / 2-10V / 0-5V
Output scaling.
Output mode
Direct / Reversed
Controller output direction.
Fixed output
OFF / 100% / 75% /
50% / 25% / 0%
Fixed output.
Deactivation
6h / 12h / 24h /
MANUAL
Fixed output deactivation timer.
1.4.2.4 Controller menu
The control output can be controlled either according to a one measurement value or according to the
maximum selection of all values.
M
OK
CONTROLLER
OFF
Cont
OK
OK
OK
OK
Modbus ID
PI
Control mode
300
Integr. time s
21.0
°C Setpoint
OK
P
Control mode
OK
HUMIDITY
Cont
OK
OK
OK
OK
Modbus ID
PI
Control mode
300
Integr. time s
50
%RH Setpoint
OK
P
Control mode
OK
MAXIMUM CTRL
Cont
OK
OK
OK
Modbus ID
PI
Control mode
300
Integr. time s
P
Control mode
OK
OK
21.0
°C Setpoint
OK
2.0
°C Propor. band
OK
50
%RH Setpoint
OK
OK
+/-
+/-
+/-
+/-
+/-
+/-
TEMPERATURE
Cont
50
%RH Propor. band
50
%RH Propor. band
2.0
°C Propor. band