POTENTIOMETER
OK
M
Y4
POT USAGE
OK
Y3
POT USAGE
OK
+/-
+/-
OK
TE-SP
POT USAGE
+/-
OK
TE-SP CENTER °C
21.0
OK
RH-SP
POT USAGE
+/-
OK
RH-SP MIN
40
OK
RH-SP MAX
60
OFF
POT USAGE
Parameter
Available values
Description
POT USAGE
OFF / Y3 / Y4 / TE-SP /
RH-SP
Controlled value.
OFF
Potentiometer is not in use.
Y3
Potentiometer output is Y3.
Y4
Potentiometer output is Y4.
Note:
You have to set the controller
off, if the potentiometer is configured
to Y4 output.
TE-SP
Potentiometer is used to set the temperature
setpoint. The potentiometer adjustment range is
±3 °C around the set point centre.
RH-SP
Potentiometer is used to set the humidity
setpoint.
TE-SP CENTER
°C
10.0...30.0 °C
Temperature setpoint centre. The value can be adjusted by 0.1 °C
steps.
RH-SP MIN
0...100 %
Humidity setpoint range, low limit. The value can be adjusted by
5 % steps.
RH-SP MAX
0...100 %
Humidity setpoint range, high limit. The value can be adjusted by
5 % steps.
1.4.2.6 Relay menu
Relay menu is available in R models. The relay switching point and hysteresis can be changed through
the menu.