Published: 25.03.2022
15 (15)
Regis-
ter
Parameter description
Data type Values
Range
Default
40029
Relay function
0 - 1 - 2 - 3 - 4
0. Off
1. Not in use
2. Temperature
3. Humidity
4. Temperature,
humidity
3
40030
Potentiometer temperature
setpoint centre
S16
100...300
10.0...30.0 °C
210
40031
Potentiometer humidity setpoint
low limit
S16
0...100
0...100 %
40
40032
Potentiometer humidity setpoint
high limit
S16
0...100
0...100 %
60
40033
Not in use
S16
-
-
600
40034
Not in use
S16
-
-
1200
40035
Not in use
S16
-
-
1
40036
Not in use
S16
-
-
1
40037
Not in use
S16
-
-
2
40038
Y1…Y4 output range
S16
0 - 1 - 2
0. 0...10 V
1. 2...10 V
2. 0...5 V
0
40039
Fixed control output
S16
0 - 1 - 2 - 3 - 4
- 5
0. Off
1. 100 %
2. 75 %
3. 50 %
4. 25 %
5. 0 %
0
40040
Fixed control output timer
S16
0 - 1 - 2 - 3
0. 6 h
1. 12 h
2. 24 h
3. Manual
1