Published: 25.03.2022
7 (15)
Relay
menu
Info
menu
Software
version
Reset to factory settings
[no / yes]
M
OK
RELAY
M
OK
OK
Modbus ID
INFO
1.0.0
VERSION
no
RESET?
5 s
OK
OFF
Relay
OK
OK
OK
Modbus ID
OK
OK
OK
Modbus ID
ALL
Relay
OK
OK
OK
OK
OK
OK
Hysteresis
[0...50 %]
Relay set point
[0...100 %]
Modbus ID
50
RelON %RH
5
Hysteresis %RH
+/-
+/-
+/-
Hysteresis
[0...20 °C]
Relay set point
[0...50 °C]
TEMPERATURE
Relay
23.0
RelON °C
2.0
Hysteresis °C
Hysteresis
[0...50 %]
Relay set point
[0...100 %]
HUMIDITY
Relay
50
RelON %RH
5
Hysteresis %RH
Hysteresis
[0...20 °C]
Relay set point
[0...50 °C]
23.0
RelON °C
2.0
Hysteresis °C
1.4.2.1 Communication menu
Communication menu is available in M models.
M
OK
OK
OK
OK
Modbus ID
COMMUNICATIONS
1
MODBUS ID
9.6
Baud rate (k)
n
Parity
Parameter
Available values
Description
MODBUS ID
OFF / 1...247
Modbus address.
Baud rate (k)
9.6 / 19.2 / 34.8 /
56.0 / 57.6 / 76.8 /
115.2
Modbus speed (kbit/s).
Parity
n / E / O
Parity bit.
n
None
E
Even
O
Odd
1.4.2.2 Calibration menu
All the measurements can be tuned through the calibration menu.
M
OK
CALIBRATION
OK
0.0 (22.6)
Offset: °C
OK
0 (30)
Offset: %RH
Parameter
Available values
Description
Offset °C
-3.0...3.0
Temperature measurement tuning. The value can be adjusted by
0.1 °C steps.
Offset %RH
-5...5
Humidity measurement tuning, RH models. The value can be
adjusted by 1 % steps.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | [email protected]
Information is subject to change without prior notice.
EN - 1132210ug