Published: 25.03.2022
13 (15)
Example:
1. The register value range is -500…500.
2. You try to write the value 600 to the register.
3. The value 500 is written to the register.
2.4.1 Coils
Regis-
ter
Parameter description
Data type Values
Range
Default
1
Y1 output overdrive activation
Bit
0 - 1
0. Off
1. On
0
2
Y2 output overdrive activation
Bit
0 - 1
0. Off
1. On
0
3
Y3 output overdrive activation
Bit
0 - 1
0. Off
1. On
0
4
Y4 output overdrive activation
Bit
0 - 1
0. Off
1. On
0
5
Relay overdrive activation
Bit
0 - 1
0. Off
1. On
0
6
Relay overdrive
Bit
0 - 1
0. Off
1. On
0
7
Controller output direction
Bit
0 - 1
0. Direct
1. Reversed
0
2.4.2 Discrete inputs
Register Parameter description
Data type Values
Range
10001
Relay status
Bit
0 - 1
0. Off
1. On
2.4.3 Input registers
Register Parameter description
Data type Values
Range
30001
Not in use
S16
-
-
30002
Temperature measurement
S16
0...500
0.0...50.0 °C
30003
Humidity measurement
S16
0...100
0...100 %rH
30004
Y1 output voltage
U16
0...1000
0.00…10.00 V
30005
Y2 output voltage
U16
0...1000
0.00…10.00 V
30006
Y3 output voltage
U16
0...1000
0.00…10.00 V
30007
Y4 output voltage
U16
0...1000
0.00…10.00 V
30008
Active potentiometer value
U16
0...1000
0.00…10.00 V
30009
Active potentiometer setpoint value
U16
variable
variable
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | [email protected]
Information is subject to change without prior notice.
EN - 1132210ug