2.4.4 Holding registers

Regis-

ter

Parameter description

Data type Values

Range

Default

40001

Y1 output overdrive

S16

0...1000

0...10.00 V

0

40002

Y2 output overdrive

S16

0...1000

0...10.00 V

0

40003

Y3 output overdrive

S16

0...1000

0...10.00 V

0

40004

Y4 output overdrive

S16

0...1000

0...10.00 V

0

40005

Not in use

S16

-

-

0

40006

Temperature measurement tuning

(offset)

S16

-30...30

-3.0...3.0 °C

0

40007

Humidity measurement tuning

(offset)

S16

-5...5

-5...5 %rH

0

40008

Control method

S16

0 - 1

0. P
1. PI

1

40009

Controller output

S16

0 - 1 - 2 - 3 - 4

0. Off
1. Not in use
2. Temperature
3. Humidity
4. Maximum

selection

0

40010

Set point, CO

2

S16

400...10000

400...10000 ppm

700

40011

Set point, temperature

S16

0...500

0.0...50.0 °C

210

40012

Set point, humidity

S16

0...100

0...100 %rH

50

40013

Proportional band, CO

2

S16

100...10000

100...10000 ppm

500

40014

Proportional band, temperature

S16

10...320

1.0...32.0 °C

20

40015

Proportional band, humidity

S16

10...100

10...100 %rH

50

40016

Integration time

S16

50…5000

50…5000 s

300

40017

Active potentiometer usage

S16

0 - 1 - 2 - 3 - 4

0. Off
1. Y3
2. Y4
3. Temperature

setpoint

4. Humidity setpoint

2

40018

Not in use

S16

-

-

1100

40019

Not in use

S16

-

-

5

40020

Not in use

S16

-

-

750

40021

Not in use

S16

-

-

1250

40022

Value shown on the display

S16

0 - 1 - 2 - 3

0. Not in use
1. Temperature
2. Humidity
3. Scrolling

3

40023

Not in use

S16

-

-

1

40024

Not in use

S16

-

-

0

40025

Relay set point, temperature

S16

0...500

0.0...50.0 °C

230

40026

Relay hysteresis, temperature

S16

0...200

0.0...20.0 °C

20

40027

Relay set point, humidity

S16

0...100

0...100 %rH

50

40028

Relay hysteresis, humidity

S16

0...50

0...50 %rH

5

Produal Oy | Keltakalliontie 18, FI 48770 Kotka, Finland | tel. +358 10 219 9100 | [email protected]

Information is subject to change without prior notice.

EN - 1132210ug

Содержание KLH

Страница 1: ...KLH Room humidity transmitter controller User Guide This user guide is for devices with the software version 1 3 6 or newer...

Страница 2: ...to the device 4 1 4 2 ML SER menu 5 2 Modbus 12 2 1 Modbus properties 12 2 2 Terminating Modbus 12 2 3 Modbus function codes 12 2 4 Modbus registers 12 2 4 1 Coils 13 2 4 2 Discrete inputs 13 2 4 3 I...

Страница 3: ...flow coming from ventilation nozzles air flow coming from the flush mounting box differential temperature caused by external wall 1 2 Wiring CAUTION Device wiring and commissioning can only be carrie...

Страница 4: ...odels is configured to change the controller setpoint the setpoint is shown on the display when the potentiometer is rotated Press the S1 button to stop the scrolling to the currently displayed value...

Страница 5: ...M button The values can be changed with the and buttons The menu is device specific and the content depends on the device and installed options The following menu structure contains the factory setti...

Страница 6: ...ontrol mode OK HUMIDITY Cont OK OK OK OK Modbus ID PI Control mode 300 Integr time s 50 RH Setpoint OK 50 RH Propor band P Control mode OK MAXIMUM CTRL Cont OK OK OK OK Modbus ID PI Control mode 300 I...

Страница 7: ...available in M models M OK OK OK OK Modbus ID COMMUNICATIONS 1 MODBUS ID 9 6 Baud rate k n Parity Parameter Available values Description MODBUS ID OFF 1 247 Modbus address Baud rate k 9 6 19 2 34 8 5...

Страница 8: ...75 50 25 0 Fixed output Deactivation 6h 12h 24h MANUAL Fixed output deactivation timer 1 4 2 4 Controller menu The control output can be controlled either according to a one measurement value or acco...

Страница 9: ...m selection control the control output signal is formed according to the measurement that causes the largest control signal value The following situation is described in the example figure Temperature...

Страница 10: ...erature setpoint The potentiometer adjustment range is 3 C around the set point centre RH SP Potentiometer is used to set the humidity setpoint TE SP CENTER C 10 0 30 0 C Temperature setpoint centre T...

Страница 11: ...C 0 50 0 Set point for temperature C The value can be adjusted by 0 1 C steps Hysteresis C 0 0 20 0 Hysteresis for temperature C The value can be adjusted by 0 1 C steps RelON RH 0 100 Set point for h...

Страница 12: ...Modbus function codes Decimal Hexa decimal Function 1 0x01 Read Coils 2 0x02 Read Discrete Inputs 3 0x03 Read Holding Registers 4 0x04 Read Input Registers 5 0x05 Write Single Coil 6 0x06 Write Singl...

Страница 13: ...1 Reversed 0 2 4 2 Discrete inputs Register Parameter description Data type Values Range 10001 Relay status Bit 0 1 0 Off 1 On 2 4 3 Input registers Register Parameter description Data type Values Ra...

Страница 14: ...013 Proportional band CO2 S16 100 10000 100 10000 ppm 500 40014 Proportional band temperature S16 10 320 1 0 32 0 C 20 40015 Proportional band humidity S16 10 100 10 100 rH 50 40016 Integration time S...

Страница 15: ...ometer humidity setpoint high limit S16 0 100 0 100 60 40033 Not in use S16 600 40034 Not in use S16 1200 40035 Not in use S16 1 40036 Not in use S16 1 40037 Not in use S16 2 40038 Y1 Y4 output range...

Отзывы: