2.4.4 Holding registers
Regis-
ter
Parameter description
Data type Values
Range
Default
40001
Y1 output overdrive
S16
0...1000
0...10.00 V
0
40002
Y2 output overdrive
S16
0...1000
0...10.00 V
0
40003
Y3 output overdrive
S16
0...1000
0...10.00 V
0
40004
Y4 output overdrive
S16
0...1000
0...10.00 V
0
40005
Not in use
S16
-
-
0
40006
Temperature measurement tuning
(offset)
S16
-30...30
-3.0...3.0 °C
0
40007
Humidity measurement tuning
(offset)
S16
-5...5
-5...5 %rH
0
40008
Control method
S16
0 - 1
0. P
1. PI
1
40009
Controller output
S16
0 - 1 - 2 - 3 - 4
0. Off
1. Not in use
2. Temperature
3. Humidity
4. Maximum
selection
0
40010
Set point, CO
2
S16
400...10000
400...10000 ppm
700
40011
Set point, temperature
S16
0...500
0.0...50.0 °C
210
40012
Set point, humidity
S16
0...100
0...100 %rH
50
40013
Proportional band, CO
2
S16
100...10000
100...10000 ppm
500
40014
Proportional band, temperature
S16
10...320
1.0...32.0 °C
20
40015
Proportional band, humidity
S16
10...100
10...100 %rH
50
40016
Integration time
S16
50…5000
50…5000 s
300
40017
Active potentiometer usage
S16
0 - 1 - 2 - 3 - 4
0. Off
1. Y3
2. Y4
3. Temperature
setpoint
4. Humidity setpoint
2
40018
Not in use
S16
-
-
1100
40019
Not in use
S16
-
-
5
40020
Not in use
S16
-
-
750
40021
Not in use
S16
-
-
1250
40022
Value shown on the display
S16
0 - 1 - 2 - 3
0. Not in use
1. Temperature
2. Humidity
3. Scrolling
3
40023
Not in use
S16
-
-
1
40024
Not in use
S16
-
-
0
40025
Relay set point, temperature
S16
0...500
0.0...50.0 °C
230
40026
Relay hysteresis, temperature
S16
0...200
0.0...20.0 °C
20
40027
Relay set point, humidity
S16
0...100
0...100 %rH
50
40028
Relay hysteresis, humidity
S16
0...50
0...50 %rH
5