Parameter
Name on LCD
& Icon
Explanation of Parameter
Factory Setting
Setting Range
System Config DGC202X provides complete flexibility in
system designing. This parameter defines
the system configuration in terms of the
mains and generator connections (Phases
1P or 3P)
Please note that the phases are defined
w.r.t to the input to the panel
AMF-M: 3P/G:3P
AMF-M: 3P/G:1P
AMF-M: 3P/G:3P
AMF-M: 1P/G:1P
CAN J1939
CAN Bus enable/disable.
DGC202X can be used engine with CAN
bus or without this bus.
Disabled
Disabled*
Enabled
Solenoid Type Pull to Start
Cranking command occurs after the
solenoid pre time set in generator
parameter. Fuel solenoid is kept pull till
the time engine is running. To stop engine
it is released
Pull to Stop
Fuel solenoid is pulled to stop the engine
for a pre-programmed duration.
Pull to stop
Pull to Stop
Pull to Start
C A N
LLOP Sensor
Type
Select the installed sensor for LLOP.
There are many built in sensors to choose
from. For sensors whose data is not in-
built User defined can be selected and the
sensor data programmed. Below twenty
parameters are for programming the User
defined sensors. If a in-built sensor is
selected the following twenty parameter
shall not be displayed
TYPE A
User Defined
Type A
M&M
MNEPL
VE
TMTL
HUAFANG
TATA
GC(VDO)
GC(MURPHY)
4-20 ma
Disabled *
4-20Max
Range
Max.Rangeof4-20mALLOPSensor. 40
2-40
LLOP
Sensor R1
R1 to R10 = Resistance Value
V1 to V10 = Corresponding pressure
value.
These table are used when sensor type is
selected as user defined.
10
0-999