Digital Input 4
Delay
Monitoring time for programmable digital
input. Digital inputs are explained above.
5
1-100 Sec
Digital Input 5
Delay
Monitoring time for programmable digital
input. Digital inputs are explained above.
5
1-100 Sec
Digital Input 6
Delay
Monitoring time for programmable digital
input. Digital inputs are explained above.
5
1-100 Sec
ChgALt Vol
The minimum voltage for the charging
alternator for a healthy charging
alternator/V-Belt.
Disabled Disabled*
5-30
Chg Alt-
V Belt Delay
Duration for which the above voltage
should fall below the set limit for the
engine to be stopped on fault.
Disabled Disabled*
1-30 Sec
Hooter ON TimeDuration for which the hooter shall be
ON, if not externally reset, while
announcing a fault.
30
1-100 Sec
Crank ON Time Maximum crank time.
5.0
1.0-20.0 Sec
Crank GapTime The delay between two successive cranks.5
1-200 Sec
Crank Attempts The maximum number of cranks that
shall be attempted to start the Engine.
3
1-10
Solenoid ON
time
The time for which stop solenoid will be
kept active while stopping the engine.
Please note that in case of PULL to Start
mode this time should be reduced
(recommended 5 sec).
22
1-100 Sec
Priming Delay The duration at which the stop solenoid
to go in the fuel shut-off mode and
simultaneously shall start the cranking
command when the start command is
initiated.
Disabled 1.1-9.9 Sec
Disabled*
N