14.3 Mains Parameter
Over Voltage
Max. Permissible Mains voltage, above this
the mains voltage is treated unhealthy and
Generator is started.
270V
50-300V
Under
Voltage
Min. Permissible Mains voltage, below this
the mains voltage is treated unhealthy and
Generator is started.
180V
50-300V
Mains Voltage
Delay
Duration for which Mains Over/Under
voltage condition can be tolerated before
starting the Generator.
10
1-999 Sec
Over
Frequency
Max. Permissible Mains frequency, above
this frequency the Mains is treated
unhealthy & Generator is started.
65.0
40.0-69.9Hz
Disabled*
Mains U/F Min. permissible Mains frequency, below
this frequency the Mains is treated
unhealthy & Generator is started.
45.0
Disabled*
40.1-70.0Hz
Mains Freq
Delay
Duration for which Mains Over/Under
frequency condition can be tolerated
before starting the Generator.
5
1-999 Sec.
Voltage
Unbalance
Max. allowed voltage unbalance in
volt.
Disabled 10-99Volt
Disabled*
Voltage
Unbalance
Delay
Duration for which unbalance can be
allowed before starting the Generator. This
parameter is not available if above is set to
disabled.
10
1-999Sec
H
z
H
z
H
z
A
A