B.Light Dim % Backlight brightness while there is no
event, such as Key pressed, fault or
warning.
In normal case the display brightness
shall reduce to this level after 120 sec of
no event.
50
0-100
LCD Contrast For increasing or decreasing the Display
Contrast.
10
1-20
Battery UV
Warning
Min. permissible battery voltage, below
this the voltage is treated unhealthy &
warning is generated.
Disabled Disabled*
9.1-35.0V
Battery OV
Warning
Max. permissible battery voltage, above
this the voltage is treated unhealthy &
warning is generated.
Disabled 9.0-34.9V
Disabled*
15.5 Comm RS485 Parameter
Device Id
Modbus device ID.
1
1-247
Baud Rate
RS-485 Communication Baud rate.
9600
1200
2400
4800
9600
19200
Parity
RS-485 Communication Parity Bits.
None
Even
Odd
None
Stop Bits
RS-485 Communication Stop Bits.
1
1
2
Prime Off Hr The duration after which the priming
function again works after the last engine
stop.
24
0-99 Hr
Auto Scroll
Setting ON will enable Auto Scroll of
display. OFF: No scroll and next
parameter can be viewed by pressing
next switch.
Auto
Scroll On
Auto Scroll On
Auto Scroll Off