10 

EmpyrE ElItE InstallatIOn and OpEratIOn manual

InsTallaTIon

Installation Instructions

We recommend that the furnace be installed by a 

qualified installer.

1. Identify and remove components shipped in the 

furnace firebox or rear of furnace: water level indicator, 

ash rake, flue cleaning brush and rods, and lifting hook. 

Leg extensions, leg braces with bolt packages are 

optional.
2. Move the furnace by using the lifting hook or lifting 

from the bottom. CAUTION: Furnace is heavy. To make 

handling easier the brick may be removed. 

lifting Hook Installation

1.  Locate hook in furnace package.
2.  Remove plug from top of furnace.
3.  Securely screw hook into thread on furnace.

Empyre Elite dismantling/assembly Instructions 

In the event where the Empyre Elite furnace needs to 

be dismantled to reduce weight and size follow these 

instructions.
To reduce the weight by 150 lbs (68 kg) remove the 

brick. Observe brick placement before removing brick 

and re-install the brick accordingly. Also refer to page 

26 and 27. To further reduce weight, remove the loading 

and ash door. Take note of any hinge spacer washers 

and re-install accordingly.
To reduce size and weight the top, side panels and bottom 

may be removed. 

note: the next steps involve electrical 

components  and  should  only  be  done  by  a  qualified 

electrician

.

1. Disconnect wiring in the back of the furnace: remove 

access cover; unplug wires from snap disc; remove 

temperature probe (use Allen wrench or Philips screw 

driver); undo connectors on the blower wires; slip cord 

strain relief out of its mount.
2. Remove 4 bolts from the top panel. Lift front slightly 

to remove the switch trigger bolt, and then fully remove 

the top panel. (Note: if switch trigger pulls out of the 

control box, follow these instructions to re-install the 

switch trigger: remove the control front plate to view the 

inside of the control box; guide the switch trigger into 

the slot next to the limit switch.)
3. Remove the side panel: remove door lock bars and 

front and back bolts; pull panel to the back until it can 

pull away from the furnace. 
4. Remove bottom: remove bolts and drop pan down.
5. To install components, reverse steps 1-4. Refer 

to page 8 and the electrical diagram on page 23 for 

assistance.

Chimney Installation

When installing a new chimney flue, be sure to observe 

local building codes and the National Fire Protection 

Association rule: the top of the chimney must extend at 

least 3.0 feet (0.9 m) above the highest point where it 

exits the roof and be at least 2.0 feet (0.6 m) taller than 

any point of the roof within 10.0 feet (3.04 m).
For a new chimney, use an insulated stainless steel system 

that conforms to type HT (High Temperature) requirements of 

UL 103 and ULC-S629 and complies with the requirements of 

Chapter 11 of NFPA 211, Standard for Chimneys, Fireplaces, 

Vents and Solid Fuel Burning Appliances.

The furnace comes with a 6” (15 cm) flue collar. The rec

-

ommended chimney size is 6” (15 cm). A larger than 6” 

chimney size may result in reduced performance.
Chimney connectors must be a minimum of 24 gauge 

black or blued steel.
A chimney cap must be installed.
Lining masonry chimneys with a stainless steel liner is 

recommended.

note:

 For good chimney draft, connecting stove pipe elbows  

between furnace and chimney must not be 90°; 45° is 

recommended. The shorter the stove pipe connection the  

better. Make sure to follow local building codes. 

note: Incorrect chimney installation will void the warranty.

This is a forced air furnace but it is important that the chim-

ney has good draft to further eliminate any smoke issues. 

ImpOrtant:

 A spark arrester must be installed if the fur-

nace is used in a high fire risk area.

Содержание Empyre Elite 100

Страница 1: ...Installation and Operation Instructions Empyre Elite Model 100 and 200...

Страница 2: ......

Страница 3: ...stallation 10 Supplying Make Up Air 11 Low Water Temperature Protection 11 Empyre System Optimizer 11 Electrical Hookup 12 Water Line Hookup 12 Side Arm Installation 14 Optional Heat Exchanger 14 Auxi...

Страница 4: ...Switch DTS 22 Hot Water Wood Furnace Wiring Diagram 23 How to Correct a Sticking Flapper 24 Furnace Specifications 25 Furnace Options 25 Ash Rake and Brush Hanger Assembly 25 Unit Dimensions Model 100...

Страница 5: ...ed wood gasification to produce highly efficient combustion in the furnace s dual burn chambers 1 Wood in the firebox burns from the bottom up drying the top layer of wood in the firebox and forcing g...

Страница 6: ...ax Combustion Blowers Empyre Elite 100 70211231 Fuel Burn wood only Floor May be installed on a well constructed combustible floor A noncombustible liner must be placed underneath the furnace at least...

Страница 7: ...OOR ALWAYS OPEN SLOWLY 1 ALWAYS switch furnace off before opening door DO NOT operate with ash removal door open 2 CLOSE and LATCH door firmly CAUTION Keep children a safe distance from the furnace DO...

Страница 8: ...lly hazardous situation that if not avoided MAY result in minor or moderate injury if proper practices are not taken or serves as a reminder to follow appropriate safety practices Safety Decals Please...

Страница 9: ...Empyre Elite Installation and Operation Manual 7 Safety 1 3 4 5 7 6 Front View 1 2 3 Rear View 6 4 5 7 2...

Страница 10: ...Operation Manual Features Identifying Main Components see list of components on page 9 47 46 45 48 1 10 12 9 8 7 6 5 4 3 2 11 42 43 41 40 39 38 44 26 27 14 13 28 29 30 16 15 19 17 18 31 21 22 23 25 1...

Страница 11: ...urnace 12 305 mm Front of Furnace to Combustibles 48 1220 mm Flue Pipe 12 305 mm Ceiling to Furnace 24 610 mm Floor 0 0 mm Installation Requirements 1 The Empyre Elite must be installed on a level sta...

Страница 12: ...ontrol box follow these instructions to re install the switch trigger remove the control front plate to view the inside of the control box guide the switch trigger into the slot next to the limit swit...

Страница 13: ...m Low Water Temperature Protection It is the Responsibility of the installer to provide low water temperature protection in the design of the heat distribution system The Empyre Elite furnace is no di...

Страница 14: ...s recommended that a line be installed between the overflow port and suitable catch pan or drain 1 Hook up supply to Supply port and return to Return port as indicated see page 8 2 Install shut off va...

Страница 15: ...eeds and will conform to all local codes The Pro Fab Industries warranty covers the Empyre Elite furnace only and does not include anything outside of the Empyre Elite furnace Pro Fab Industries takes...

Страница 16: ...rm as low as possible PUMP BALL VALVE THERMOMETER BOILER DRAIN TEMPERING OR MIXING VALVE SYMBOLS INDEX Side Arm Installation To domestic heating system Hot water in from Empyre Elite furnace To top of...

Страница 17: ...door Furnace runs out of wood Figure 1 Note The existing furnace functions as a standby The aquastat on the standby furnace should be turned lower than the aquastat on the Empyre Elite Auxiliary Heat...

Страница 18: ...ow Check water level again 8 Add Pro Fab approved water treatment through vent opening Figure 1 9 Check water level when water temperature is 170 F 77 C and add water until level indicator shows full...

Страница 19: ...n burning extremely dry firewood pieces should be over 5 12 7 cm in diameter If using high moisture wood use pieces that are less than 5 12 7 cm in diameter It is good to mix the dry and wet wood when...

Страница 20: ...out of the firebox gently rake it into the secondary burn chamber through the opening in the bottom of the firebox It is important to rake ash buildup away from the back wall of the firebox 1 Do this...

Страница 21: ...vate by moving the lever fully to the right and then back to the left 3 Close door securely and move lever fully to the right Note if the lever is not fully to the right the buzzer will remain on and...

Страница 22: ...at exchanger flues weekly A buildup in the flues and chimney will cause a poor draft and reduce efficiency 6 Check and clean the air passages in the upper loading door frame several times during the h...

Страница 23: ...the water reservoir is full during the non heating season to prevent corrosion inside the water jacket 8 Add the correct amount as indicated on water treatment bottle of Pro Fab approved water treatm...

Страница 24: ...rcuit probe error Open probe error DTS Technical Data Accuracy 1 Output 16 Amp 1HP 240 Vac SPDT relay Supply voltage 115 Vac 10 Display 3 digit red DTS Programming Press SET SP text will appear on the...

Страница 25: ...23 Reference CAUTION DO NOT CONNECT THE ELECTRICAL COMPONENTS OF THIS UNIT TO ANY OTHER ELECTRICAL APPLIANCE DO NOT modify the electrical components or any other part of this furnace Modification to a...

Страница 26: ...Persist 1 Check if furnace is being operated properly 2 Remove flapper unit check to ensure the flap seals in the closed position clean and oil How to Remove and Reinstall 1 Disconnect power 2 Remove...

Страница 27: ...el type and quality For overall unit dimensions see Figure 1 Model 100 on page 26 Model 200 on page 27 For brick layout see Figure 2 Model 100 on page 26 Model 200 on page 27 For refractory layout see...

Страница 28: ...on Manual Reference Model 100 3 1 4 1 2 Not shown 0 817753 Revisions DESCRIPTION ECO Production Release 2535 REV 3 1 4 1 2 Not shown 817753 Figure 2 Brick Layout Figure 3 Refractory Layout Figure 1 Un...

Страница 29: ...PRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF IS PROHIBITED PRINT DATE 10 05 11 CHECKED DRAWN DATE NAME DO NOT SCALE DRAWING Material Spec MATERIAL DWG NO SCALE 1 20 Pro Fab Indus...

Страница 30: ...air passage in the firebox floor is blocked by charcoal ash Using the ash rake always stir the firebox charcoal ash into the lower ash chamber before adding wood Limit the charcoal ash buildup and let...

Страница 31: ......

Страница 32: ...ranty Registration and a copy of the original bill invoice must be forwarded to Pro Fab within thirty 30 days of the date of purchase to validate the warranty Issue Date February 2013 Part No 817941R0...

Отзывы: