![Princeton GTIB-30 Скачать руководство пользователя страница 59](http://html1.mh-extra.com/html/princeton/gtib-30/gtib-30_installation-manual_1603033059.webp)
GTIB-30 Installation Manual-UL
4411-0011, Rev 2.0
59
5.2 Commissioning Checklist
√
Item
Info
All Systems
Open External Load Port Disconnect
Open External Grid Port Disconnect
Open External DC disconnect
Open Integrated Grid switch (if
installed)
Open Integrated DC switch
If the DC port is connected to Battery
a.
Measure and verify battery
voltage on battery side of
External DC disconnect in
range
Must be < 600V.
b.
Visually check battery
polarity if possible.
c.
Close External DC
disconnect
Ensure internal DC disconnect is open!
d.
Check polarity of battery
voltage on terminal blocks
inside GTIB-30
24V Power supply inside GTIB-30 will
power up if batteries sufficiently charged.
e.
Close integrated battery
switch
If DC port is connected to PV array
a.
Measure and verify PV
voltage on PV array side of
External DC disconnect
Must be <600V
b.
Visually check PV polarity if
possible
c.
Close External DC disconnect
d.
Check polarity of PV voltage
on terminal blocks inside
GTIB-30
e.
Close integrated DC
disconnect
Содержание GTIB-30
Страница 1: ...Clean power made simple GTIB 30 Installation Manual ...
Страница 2: ...www princetonpower com 4411 0011 Rev 2 0 April 1st 2014 ...
Страница 11: ...About this Manual 4411 0011 Rev 2 0 xi This page intentionally left blank ...
Страница 15: ...Contents 4411 0011 Rev 2 0 15 This page intentionally left blank ...
Страница 16: ...1 Introduction ...
Страница 18: ...2 System Overview and Configurations ...
Страница 31: ...3 Pre Installation ...
Страница 36: ...GTIB 30 Installation Manual UL 36 4411 0011 Rev 2 0 This page intentionally left blank ...
Страница 37: ...4 Wiring Instructions ...
Страница 56: ...GTIB 30 Installation Manual UL 56 4411 0011 Rev 2 0 This page intentionally left blank ...
Страница 57: ...5 Commissioning Sequences ...
Страница 61: ...GTIB 30 Installation Manual UL 4411 0011 Rev 2 0 61 This page intentionally left blank ...
Страница 62: ...A GTIB 30 kW Specifications ...
Страница 65: ...GTIB 30 Installation Manual UL 4411 0011 Rev 2 0 65 This page intentionally left blank ...
Страница 66: ...B Return Material Authorization Contact and Product Information ...
Страница 69: ...GTIB 30 Installation Manual UL 4411 0011 Rev 2 0 69 This page intentionally left blank ...